connected to the same circuit, the total electrica! load must be
considered
in selecting the proper wire size DO NOT USE
UNDERSIZE
WIRE
FUSES., Refer to the National Electric Code to determine
the proper
fuse or circuit breaker rating required. When selecting
fuses,
remember the momentary
starting current of an electric motor is
greater than its full load current
Time-delay
or "slow-blow" fuses
are recommended.
Single-Phase
Wiring
uJ
L=J
L1
T = Supply Line Terminal
L = Load Terminal
used disconnecLor clrcu_t breaker
Pressure switch
(inctltde_ on/auto-off
switch)
Singie phase
m_or
COMPRESSOR
LUBRICATION
CAUTION
Do not operate without lubricant
or with inadequate
lubricant.
Ingersoll-Rand fs not responsible for
compressor failure caused by inadequate
lubrication
SYNTHETIC
LUBRICANT.
We recommend
thgersolI-Rand
synthetic compressor
lubricant from start-up
See the WARRANTY
section for extended warranty information
ALTERNATE
LUBRfOANTS.
You may use a petroleum-based
lubricant that is premium quality, does not contain detergents,
contains only anti-rust, anti-oxidation,
and anti-foam
agents as
additives,
has a fieshpoint of 440°F (227°C) or higher, and has an
auto-ignition
polnt of 650=F (343°C) or higher
See the petroleum lubricant viscosity table below The table is
intended as a general guide only Heavy duty operating conditions
require heavier viscosities,, Refer specific operating conditions
to
_our dealer for recommendations
Temperature Around Unit
Vlscosib' @ 100"F (37 8"C)
Viscosity Grade
_F
"C
SUS
Centtstokes
1SO
SAE
40 & below
4 4 & below
150
32
32
10
40 - BO
4 4 - 26 7
500
t10
!00
30
80 - 125
26.7 - 51.0
750
165
'_50
40
you use
a petroleum-based
compressor
lubricant
at start-up
and
decide
to convert
to Ingersoll-Rand
synthetic
compressor
lubricant
later
on, the compressor
valves
must
be thoroughly
decarbonized
and the crankcase
must
be flushed
before
conversion
FILLING PROCEDURES:
t,, Unscrew and remove the ell fill plug (A)
2.
Slowly flit the crankcase with lubricant until the lubricant reaches the
top thread of the sit filI opening and the top of the sight glass
Crankcase capacity for the SS3 Is one-half (0 5) Iiter Crankcase
capacity for the SS5 is one (1) liter.,
3.
Replace the oil fill plug HAND TIGHT ONLY
Filling Procedures
INITIAL
START-UP
Follow this procedure
before putting the unit into service for the first
time:
t.
Set the pressure swffch lever to "OFF"..
Pressure Switch Lever
OFF"
ON/AUTO
2.
Open the service valve fully to prevent air pressure from building in
the tank. (A=Open, B=Closed)
Service Valve
3.
Move the pressure switch lever to "ON/AUTO _ The unit will start
4.
Run the unit for 30 minutes Ensure the service vaive is fully open
and there is no tank pressure build up
CAUTION
Unusual noise or vibration indicates a problem
Do
not continue to operate until you identify and
correct the source of the problem., IF EMERGENCY
CONDITIONS ARE ENCOUNTERED, SHUT OFF THE
MAIN POWER IMMEDIATELY,
5.,
After
30 minutes,
close the service
valve fully. The air receiver
will fill
to cut-out
pressure
and the motor will stop
The unit is now ready for
use
B[o] "J =1 :_.,_ II[=]h
GENERAL
Your air compressor
was designed for f 00% continuous
duty
operation with the use of Ingersoll-Rand
synthetic
compressor
lubricant and 60% continuous
duty operation with the use of
petroleum lubricant
In other words, synthetic
lubricant allows the
compressor
to pump continuously
without cycling
Petroleum
lubricant limits the compressor
to a maximum of 36 minutes of
pumping time per hour The compressor
should not cycle more than
10 times per hour