Mitsubishi City Multi PEFY-P72NMHSU-E Technical & Service Manual page 10

R410a
Table of Contents

Advertisement

2. Electrical component specifications
Component
Room temperature
thermistor
Liquid pipe thermistor
Gas pipe thermistor
Fuse (INV board)
Fuse (NF board)
Fuse (NF board)
Fan motor
Linear expansion valve
Power supply terminal
block
HWE10170
Symbol
TH21
Resistance 32°F (0°C)/15kΩ, 50°F (10°C)/9.6kΩ, 68°F (20°C)/6.3kΩ,
77°F (25°C)/5.4kΩ, 86°F (30°C)/4.3kΩ, 104°F (40°C)/3.0kΩ
TH22
Resistance 32°F (0°C)/15kΩ, 50°F (10°C)/9.6kΩ, 68°F (20°C)/6.3kΩ,
77°F (25°C)/5.4kΩ, 86°F (30°C)/4.3kΩ, 104°F (40°C)/3.0kΩ
TH23
Resistance 32°F (0°C)/15kΩ, 50°F (10°C)/9.6kΩ, 68°F (20°C)/6.3kΩ,
77°F (25°C)/5.4kΩ, 86°F (30°C)/4.3kΩ, 104°F (40°C)/3.0kΩ
F01
F001
F100
MF
LEV1
12VDC Stepping motor drive port diameter ø3.2 (0~2000 pulse)
LEV2
TB2
250V 15A
250V 10A
250V 3.15A
8-pole, Output 870W ERC8801AB
(L, N,
) 450V 30A
- 4 -