2
C H A P T E R
by the scaling factor at a given temperature. The scaling factor is often
represented as the ratio R
For example, if the thermistor is rated as a 10 Kohm thermistor, then R25 =
10,000 ohms (the resistance at 25C). To find the resistance at 10C, find the ratio
factor at 10C as supplied by the manufacturer. If the ratio was 1.99, then the
resistance at 10C would be 10,000 x 1.99 = 19,900 ohms.
Table 2.1 shows some typical values of resistance ratios and temperatures for a
thermistor.
Table 2.1 Typical Thermistor R/T Data
Use of the Steinhart-Hart Equation
The Steinhart-Hart (S-H) equation accurately models the non-linear R-T
characteristic curve of a negative temperature coefficient (NTC) thermistor. When
the correct constants for a thermistor are known, the S-H equation can be used to
convert between resistance and temperature. This method offers the advantage of
accurately calculating R-T values at any point on the curve, not just those supplied
by the manufacturer.
There are several forms of the Steinhart-Hart equation. The form of the S-H
equation which is used by ILX Lightwave is:
T = 1/(C1 + C2(Ln R) + C3(Ln R)
where R is the resistance in ohms; C1, C2, and C3 are the Steinhart-Hart
constants for a particular thermistor
Generally, the Steinhart-Hart constants for a thermistor are not specified by the
thermistor manufacturer. These constants may be derived specifically for each
thermistor, or the nominal value for a thermistor may be used (see Appendix A).
ILX Lightwave supplies the S-H constants when a TS-510 calibrated thermistor is
purchased.
12
LDT-5412
O P E R A T I O N
Temperature from Resistance
Temperature in C
10
11
12
13
14
15
/R
.
T
25
R
/R
T
25
1.990
1.897
1.809
1.726
1.646
1.571
3
)