Ceiling Concealed Duct

9. Installation

• Please read this instruction sheet completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.
Required Parts
• Connecting cable
• Pipes: Gas side
Liquid side
• Hanging Bolt
(W 3/8 or M10 length 650mm)
• Insulated drain hose
• Additional Drain hose
(Outer Dia ................................25.4mm)

9.1 Selection of the best location

Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit's weight.
• The place should have enough area for inspection as shown
in figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimen-
sion "H" is necessary to get a slope to drain as figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
58 Universal System Air Conditioner
Air outlet vents
Air intake vents
Wired LCD Remote Control
Air filters
Required Tools
• Level
• Screw driver
• Electric drill
• Hole core drill (ø70mm)
• Flaring Tools set
• Torque Wrenches
• Hexagonal Wrench (4mm, 5mm)
• Gas-leak detector
• Owner's Manual
• Thermometer
Top view
Inspection hole
(unit: mm)
Control box
600
Front view
(600X600)
600
Front
H

Hide quick links: