Outdoor Units
(3) Two fan model(42k, 48k, 60k)
RPM step = Load_Step (42k: 9/9 step, 48k~60k:10/12 step)
+ Step Compensation by Outdoor Temp.
+ Step Compensation of temperature difference Indoor Temp. and Setting Temp
STEP TABLE
STEP-1
STEP-2
STEP-3
STEP-4
STEP-5
STEP-6
STEP-7
STEP-8
STEP-9
STEP-10
STEP-11
STEP-12
STEP-13
Min. RPM
Max. RPM
Step Compensation by Outdoor Temp.
(Cooling)
Outdoor
2 FAN
Temp.
Step_Fan + 3
45°C
Step_Fan + 2
41°C
Step_Fan + 1
38°C
Step_Fan
28°C
Step_Fan - 2
24°C
Step_Fan - 4
18°C
Step_Fan - 6
14°C
Step_Fan - 7
9°C
Step_Fan - 8
2°C
Step_Fan - 8
-5°C
Step_Fan - 8
130 Universal System Air Conditioner
RPM(Upper)
RPM(Lower)
200
OFF
200
200
250
250
300
300
400
400
500
500
600
600
700
700
750
750
800
800
850
850
900
900
950
950
200
200
950
950
(Heating)
Outdoor
Temp.
Step_Fan - 4
26°C
Step_Fan - 3
20°C
Step_Fan - 2
14°C
Step_Fan
4°C
Step_Fan + 1
-1°C
Step_Fan + 3
-7°C
Step_Fan + 4
2 FAN