Ceiling Concealed Duct

3. Specifications

Indoor unit type
Power Supply
Cooling Capacity
Heating Capacity
Current
Nominal running current
Fan
Motor Type
Fan Type
Motor Output x Number of Unit
Air Flow Rate(H/M/L)
External Static Pressure
Capacitor
Drive
Coil
Row x Columns x FPI
Dimensions(WxHxD) Body
Weight
Body
Air Filter
Sound Level (H/M/L)
Piping
Liquid
Connections
Gas
Drain(OD/ID)
Dehumidification Rate
Safety devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable outdoor unit
Power and transmission interunit cable
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Cooling/heating capacity of indoor unit can be different when it is connected to other type outdoor.
48 Universal System Air Conditioner
Model
Ø/V/Hz
kW
Btu/h
kW
Btu/h
A
cmm
cfm
mmAq
µF/Vac
mm
mm(inch)
kg(lbs)
dB(A)+3
mm(inch)
mm(inch)
mm
l/h
No.x mm
Ceilling Concealed Duct - High Static
ABNH366GLAC
ABNH426RLAC
[UB36 NGC]
[UB42 NRC]
1 / 220 ~240 / 50 1 / 220 ~240 / 50 1 / 220 ~240 / 50 1 / 220 ~240 / 50
9.8
33,500
10.8
37,000
1.42
Induction
Induction
Sirocco Fan
Sirocco Fan
272*2
32/29/26
36/32/28
1130/1024/918
1260/1120/980
10
6/370
Direct Drive
Direct Drive
3R x 10C x 21
3R x 10C x 21
1180*298*450(46.5*11.7*17.7) 1230*380*590(48.4*15.0*23.2) 1230*380*590(48.4*15.0*23.2) 1230*380*590(48.4*15.0*23.2)
38(84)
60(132)
Long life filter
Long life filter
42/39/36
42/40/38
6.35 (1/4)
9.52(3/8)
15.88(5/8)
19.05(3/4)
32/25
4
Fuse, Thermal protector for fan motor
Thermistor
Thermistor
R-410A
R-410A
LEV
Single A
Single A
2
4*0.75
ABNH486RLAC
[UB48 NRC]
11.9
13.2
40,500
45,000
13.8
14.9
47,000
51,000
3.65
3.65
Induction
Sirocco Fan
431*2
431*2
40/35/30
1413/1236/1059
10
15
15/450
15/450
Direct Drive
3R x 13C x 19
60(132)
Long life filter
44/42/40
9.52(3/8)
19.05(3/4)
32/25
32/25
5
6
Thermistor
R-410A
LEV
LEV
Single A
4*0.75
4*0.75
Conversion Formula
= Btu/h × 0.0002931
kW
kcal/h = Btu/h × 0.252
CFM = CMM × 35.3
ABNH606RLAC
[UB60 NRC]
14.9
51,000
16.9
57,500
3.65
Induction
Sirocco Fan
431*2
50/45/40
1766/1413/1236
15
15/450
Direct Drive
4R x 13C x 19
60(132)
Long life filter
46/44/42
9.52(3/8)
19.05(3/4)
32/25
6.5
Thermistor
R-410A
LEV
Single A
4*0.75