Clearances; Vertical Installation; Horizontal Installation - Jøtul F 500 USA Installation And Operating Instructions Manual

Fireplace
Table of Contents

Advertisement

USA/cAnAdA
Jøtul F 500 Woodstove Clearances
Stove clearances
Stove- no heatshields
Single wall pipe
Stove with rear heatshield
Single wall pipe
Stove with rear heatshield
With connector shield
Stove with rear heatshield
With double wall pipe
Connector
clearances (pipe)
Single wall pipe
Single wall pipe
with connector shields
Double wall pipe
Connector
clearances (pipe)
Single wall connector
Double wall pipe
Mantel and trim

clearances

* Use of the left side load door is prohibited in alcove or
corner installations. Use Side Door Lock Kit # 155850.
18
Unprotected surface
Parallel installation
Side
Rear
14" A
18" B
355mm
460mm
14" G
10" H
355mm
255mm
14" M
6" N
355mm
150mm
14" S
6" T
355mm
150-mm
Unprotected surface

Vertical installation

18"
460mm
6"
150mm
6"
150mm
Unprotected surface

Horizontal installation

18" 460mm
6" 150mm
Stove to 1" thick or less, side trim
Stove to 1" thick or less, top trim
Stove to mantel- maximum mantel depth 12"
Protected surface NFPA 211
Parallel installation
Corner*
Side
13" C
6" D
330mm
150mm
9" I
6" J
230mm
150mm
9" O
6" P
230mm
150mm
9" U
6" V
230mm
150mm
Protected surface NFPA 211
Vertical installation
12"
300mm
6"
150mm
6"
150mm
Protected surface NFPA 211
Horizontal installation
12" 300mm
6" 150mm
Rear
Corner*
12" E
9" F
300mm
230mm
10" K
9" L
255mm
230mm
6" Q
6" R
150mm
150mm
6" W
6" X
150mm
150mm
12" 300mm
16" 410mm
30" 765mm