Annexes; Main General Specifications - Thiele SPS.Advance RT series User Manual

Uninterruptible power supply
Table of Contents

Advertisement

Vorderer Weinberg 26
• D-71522 Backnang •
8.

Annexes.

8.1.

Main general specifications.

Models:
Available powers (kVA / kW)
Technology
Input
Permissible power factor of the laods
Cold start (from batteries)
Input topology
Quantity of wires
Voltage
Voltage range
Transfer voltage:
- To battery due to low voltage mains
- Return from battery due to voltage restored
- Limit voltage Boost
- Return voltage Boost
- Limit voltage Buck
- Return voltage Buck
- To battery due to high voltage mains
- Return from battery due to voltage restored
Protection range against overvoltages
Input frequency range - Normal
Input frequency range - Genset mode
Generator set
Output
Power factor
Power (kVA)
Power (kVW)
Wave shape
Nominal voltage
Voltage accuracy (battery mode)
Voltage THD linear load
Voltage THD non-linear load
Frequency
Transfer time
Line mode to battery mode (normal mode)
Line mode to battery mode (Genset mode)
Efficiency at full load:
Line mode with charged battery
Buck mode with charged battery
Boost mode with charged battery
Battery mode
Overload on line mode
Overload on battery mode
Crest factor
Batteries (AGM sealed 3 - 5 years lifetime)
Voltage
Capacity
Quantity of batteries in serial / voltage string
Low battery voltage, block
Low battery voltage
End voltage blocking
Internal battery charger
Floating voltage per block
Maximum charging current
Recharging time (charger 1.1 or 1.5 A)
Optional charger
30
Tel.:+49 (0)7191 3560-0 (Fax.:-19)
0.750 / 0.675
1 / 0.9
1.5 / 1.35
Line interactive with sinewave output
Yes, by default with 50 Hz frequency
3 wires - Phase R(L) + Neutral (N) and earth
176 / 184 / 192 V AC (±4 %) -Normal-; 154 / 161 / 168 V AC (±4 %) -Wide ranges-
186 / 194 / 202 V AC (±4 %) -Normal-; 164 / 171 / 178 V AC (±4 %) -Wide ranges-
(45 - 55 / 55 - 65 Hz) (±0,1 Hz); Autosensing
0.750
1
0.675
0.900
1.350
< 10 %
< 12 %
With mains present, synchronised to nominal of the input (45-55 / 55-65 Hz)
Free running (battery mode) 50 / 60 ±0.1 Hz
98 %
110 % ± 10 % : 3 min.
150 % ± 10 % : 0,2 sec.
9 Ah
2 / 24V DC
3 / 36 V DC
1.1 A
1.5 A
8 hours at 90%
4 hours at 90%
-
-
SPS.ADV RT
1.5 / 1.35 (B1)
2 / 1.8
2 / 1.8 (B1)
0.9
Single phase
220 / 230 / 240 V AC
176 ÷ 288 V AC
198 / 207 / 216 V AC (±4 %)
206 / 215 / 255 V AC (±4 %)
233 / 243 / 254 V AC (±4 %)
225 / 236 / 246 V AC (±4 %)
264 / 276 / 288 V AC (±4 %)
254 / 266 / 278 V AC (±4 %)
L-N: 320V 460 Joules / 6500 A
40 - 70 Hz
Yes
0.9
1.5
2
1.8
Pure sinewave
220 / 230 / 240 V AC, selectable
± 5 %
< 3 %
< 6 %
2 - 6 ms.
13 ms as maximum
96 %
> 95 %
> 92 %
82 %
110 - 118 % : 3 min.
119 - 160% : 0,2 sec.
3:1
12 V DC
7 Ah
6 / 72 V DC
11.4 V DC
10.8 V DC block
9.6 V DC block
13.6 - 13.8 V DC
-
1.5 A
-
3 hours at 90%
7 A
-
7 A
3 / 2.7
3 / 2.7 (B1)
3
2.7
98 %
9 Ah
6 / 72 V DC
1.5 A
-
4 hours at 90%
-
7 A
USER MANUAL