2b: General Description

Quantum air compact water heaters are complete, self-contained automatic heat pump units. The
units are completely assembled, factory wired, charged, and tested prior to delivery. Each unit
consists of an air sourced fin coil evaporator, Copeland or equivalent scroll compressor, copper or
Titanium condenser, and complete refrigeration piping. Liquid line components include filter/drier,
sight-glass/moisture indicator, solenoid valve, and thermostatic or electronic expansion valve.
Other features include de-icing device, compressor heater and liquid injection device(s) for
overheat protection.
The electrical control centre includes all equipment protection and operating controls necessary for
automatic operation. Evaporator fan motors are started by their own contactors. They also have
inherent overload protection. The compressor also has solid-state motor protection for inherent
thermal overload protection.
Protection: IPX4.

2c: Inspection on Delivery

Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report
shipping damage or submit a claim to the carrier. Check the unit nameplate to be sure it agrees with the
power supply available. Units are shipped FOB factory and Quantum is not responsible for physical
damage after the unit leaves the factory. For unit shipping weights see section 2d.1: Physical Data Table.

2d: Physical Data

2d.1: Physical Data Table

PHYSICAL DATA
Compressor
Nominal (kW)
Oil, Drain/Recharge (Litre)
Refrigerant
Refrigerant Charge (kg)
Dimensions, WxDxH (mm)
Unit Shipping Weight (kg)
Optimal Water Flow (LPM)
Inlet/outlet Connections
Max Water Pressure (kPa)
Duct Connection, WxD (mm)
PHYSICAL DATA
Compressor
Nominal (kW)
Oil Drain/Recharge (Litre)
Refrigerant
Refrigerant Charge (kg)
Dimensions, WxDxH (mm)
Unit Shipping Weight (kg)
Optimal Water Flow (LPM)
Inlet/outlet Connections
Max Water Pressure (kPa)
Duct Connection, WxD (mm)
Document Number : QDC0049PD-5
67ACW2-134
67ACW2-134-C
Copeland ZR108KCE-TFD or ZR108KC-TFD with oil recharge
5.8 kg
416 kg
442 kg
70-90
70-90
DN40 Copper
DN40 Copper
1725 kPa
1725 kPa
600X500 mm
67ACP2-22
67ACP-407
ZR108KC-TFD
R22
4.6 kg
382 kg
380 kg
90-120
DN40 PVC
1725 kPa
Quantum Energy Technologies
67ACW-134
67ACW-134-C
6.7 kW
ICI EMKARATE RL 46H, 3.1/3.4
R134a
4.6 kg
1250 x 1200 x 1510 mm
392 kg
408kg
80-100
80-100
DN40 Copper
DN40 Copper
1725 kPa
1725 kPa
600X500 mm
67ACP-407-C
67ACP2-407
Copeland ZR108KCE-TFD or ZR108KC-TFD with oil recharge
6.7 kW
ICI EMKARATE RL 32H, 3.1/3.4
R407C
4.6 kg
1250 x 1200 x 1510 mm
397 kg
382 kg
90-120
DN40 PVC
1725 kPa
600X500 mm
67ACW-417
67ACW-417-C
R417A
5.8 kg
392 kg
402 kg
80-120
80-120
DN40 Copper
DN40 Copper
1725 kPa
1725 kPa
600X500 mm
67ACB-407B
67ACB-417B
R407C
R417A
5.8 kg
5.8 kg
397 kg
397 kg
90-120
90-120
DN40 PVC
DN40 PVC
1725 kPa
1725 kPa