Hot gas bypass is a system for maintaining evaporator pressure at or above a minimum value. The
purpose for doing this is to keep the velocity of the refrigerant, as it passes through the evaporator,
high enough for proper oil return to the compressor when the ambient temperature is very low.
The solenoid valve should be wired to open whenever the liquid line solenoid valve is energized.
This can be accomplished by wiring the hot gas solenoid in parallel with the liquid line solenoid.
The pressure control is factory set to begin opening at 200kPa.
The hot gas line may become hot enough to cause injury in a very short time.