2.2 INSTALLATION IN COMMERCIAL GARAGES

The Schwank Combined Intensity Heaters
are suitable for use in commercial garages
when installed in accordance with ANSI/
NFPA No. 88B 1985 (latest edition), which
states clearances to combustible construction
or material in storage, from heater and vent,
must conform to standard NFPA No. 54
(ANSI Z223.1 latest edition), in

2.3 INSTALLATIONS OTHER THAN SPACE HEATING

Use for process applications will void the
C.S.A. certification and require governing
authority field certification at the installer's /
owner's responsibility and expense.

2.4 MOUNTING CLEARANCES

The primoSchwank / supraSchwank Com-
bined Intensity Heater must be mounted with
minimum clearances as shown in sections 8.3
and 8.5. It should also be located with
WARNING:
The Schwank Combined Intensity Heaters cannot be in-
stalled inside degreasing plants, nor can they be in an area
where chlorine, fluorine or bromine are present.

2.5 HEATER MOUNTING

The Schwank Combined Intensity Heaters are
approved for both horizontal and angle
mounting. When angle mounting, the short
axis may be rotated to a maximum of 30 de-
grees. The Venturi alignment varies with NG
and LPG applications. Therefore it is very im-
IMPORTANT:
For either horizontal or angle mounting, the long axis of the heater body
must be level. Use only non-combustible mounting hardware. Diagrams 2
on page 6 illustrate typical suspension hardware that is approved.
the U.S.A. and the CSA B149, and
CAN1.2.16-M81 in Canada. "Overhead
heaters shall be installed at least (8) feet
above the floor". In addition, they shall be
located high enough to maintain the mini-
mum distance to combustibles, as shown on
the heater rating plate, between the heater
and any vehicles parked below the heater
respect to building construction and equip-
ment so as to provide sufficient clearance
and accessibility for servicing and cleaning
of burners and ignition control.
important, and critical to install the heaters
with the venturi positioned as per the manu-
facturers instructions. Improper angle
mounting can result in damage to the heater
or unsafe operation.