American Standard Inc., Tyler, TX 75711-9010
OUTDOOR UNIT 12
POWER CONNS. — V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR.
}
MAX. (AMPS)
PROT. RTG.
MIN. (AMPS)
NOISE RATING (DECIBELS) 2
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
FACTORY INSTALLED
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN — TYPE
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
LBS. — R-22 (O.D. UNIT) 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
FCCV
RESTRICTOR ORIFICE SIZE
DIMENSIONS
OUTDOOR UNIT - CRATED (IN.)
UNCRATED
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
SEER (BTU/WATT-HR.)
EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
SEER (BTU/WATT-HR.)
EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
SEER (BTU/WATT-HR.)
See page 23 for combinations with Auxiliary Devices.
18
General Data —

7A0060B100A

208/230/01/60
DURATION™- SCROLL
1 - 1
208/230/1/60
30.6 - 175
NO
YES
PROPELLER
22 - 1
DIRECT - 1
3884
1 - 1/4
825
200/230/1/60
1.90
SPINE FIN™
1 - 24
20.93
3/8
7-LBS.,12-OZ.
YES
1 1/8
3/8
0.092
H X W X D
35-3/4 X 36-3/4 X 32-1/2
SEE OUTLINE DWG.
252
229
CONDENSING UNIT WITH COOLING COILS
TXA060C5
TXA061C5
TXV-B
TXV-B
57000
59500
37500
39400
1700
1800
6.23
6.65
10.00
10.00
TXH063P3
TXV-NB
61000
43100
2000
6.49
10.55
CONDENSING UNIT WITH AIR HANDLERS
TWE048C14-B
TWE048P13
CHG TO 92
TXV-NB
57500
60000
37500
41000
1800
1800
6.46
6.42
10.00
10.50
DATA SUBJECT TO CHANGE WITHOUT NOTICE
7A0060B100A
1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER
EQUIPMENT CERTIFICATION PROGRAM, WHICH IS BASED ON A.R.I.
40
STANDARD 210/240.
60
50
2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270.
79
3 CALCULATED IN ACCORDANCE WITH NATL. ELECTRIC CODE. ONLY USE
HACR CIRCUIT BREAKERS OR FUSES.
4 STANDARD AIR - DRY COIL - OUTDOOR
5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT
NAMEPLATE AND SERVICE INSTRUCTION.
6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR -
60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID 60 FT.
FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE
PUB. NO. 12-3312-01.
7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE
AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM
BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE
SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.
8 NO MEANS NO START COMPONENTS.
YES MEANS QUICK START KIT COMPONENTS.
PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.
TXC054S3
TXC060C5
TXV-NB
TXV-B
56000
57000
37000
37500
1700
1700
6.22
6.23
10.20
10.00
TWE060C15-C/D
TWE060P13
TXV-B
TXV-NB
58000
60500
38900
41300
1950
1800
6.63
6.47
9.70
10.50
SPLIT SYSTEM
TXC061C5
TXC065S3
TXV-B
TXV-NB
59500
59500
39400
40800
1800
2000
6.65
6.43
10.00
10.40
TWE063P13
TWE065E13
TXV-NB
TXV-NB
60500
61500
41500
43000
1825
1875
6.65
6.41
10.15
10.80
TXH054A4
CHG TO 92
60000
39800
1700
6.42
10.15
TWE090A-B
TXV-NB
61500
44500
2250
6.28
10.90

Hide quick links: