7A0036A100A - American Standard ALLEGIANCE 10 Product Data

Allegiance 10 models 7a0018-060 split system cooling 1—5 ton
Table of Contents

Advertisement

PRODUCT DATA
American Standard Inc., Tyler, TX 75711-9010
OUTDOOR UNIT 12
POWER CONNS. — V/PH/HZ 3
MIN. BRCH. CIR. AMPACITY
BR. CIR.
}
MAX. (AMPS)
PROT. RTG.
MIN. (AMPS)
NOISE RATING (DECIBELS) 2
COMPRESSOR
NO. USED - NO. SPEEDS
VOLTS/PH/HZ
R.L. AMPS 7 - L.R. AMPS
FACTORY INSTALLED
START COMPONENTS 8
INSULATION/SOUND BLANKET
COMPRESSOR HEAT
OUTDOOR FAN — TYPE
DIA. (IN.) - NO. USED
TYPE DRIVE - NO. SPEEDS
CFM @ 0.0 IN. W.G. 4
NO. MOTORS - HP
MOTOR SPEED R.P.M.
VOLTS/PH/HZ
F.L. AMPS
OUTDOOR COIL — TYPE
ROWS - F.P.I.
FACE AREA (SQ. FT.)
TUBE SIZE (IN.)
REFRIGERANT
LBS. — R-22 (O.D. UNIT) 5
FACTORY SUPPLIED
LINE SIZE - IN. O.D. GAS 6
LINE SIZE - IN. O.D. LIQ. 6
FCCV
RESTRICTOR ORIFICE SIZE
DIMENSIONS
OUTDOOR UNIT - CRATED (IN.)
UNCRATED
WEIGHT
SHIPPING (LBS.)
NET (LBS.)
EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
SEER (BTU/WATT-HR.)
EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
SEER (BTU/WATT-HR.)
EXPANSION TYPE
RATINGS (COOLING) 1
BTUH (TOTAL)
BTUH (SENSIBLE)
INDOOR AIRFLOW (CFM)
SYSTEM POWER (KW)
SEER (BTU/WATT-HR.)
See pages 21 and 22 for combinations with Auxiliary Devices.
12
General Data —

7A0036A100A

200/230/1/60
DURATION™
1 - 1
200/230/1/60
16.4 - 88
YES
PROPELLER
18 - 1
DIRECT - 1
2792
1 - 1/4
1075
200/230/1/60
1.50
SPINE FIN™
1 - 24
14.83
5-LBS., 8-OZ.
YES
0.071
H X W X D
31-1/2 X 31-1/2 X 27-5/8
SEE OUTLINE DWG.
CONDENSING UNIT WITH COOLING COILS
CCBA36A4ACC
CCBB36A4ACC
FIXED ORIFICE
FIXED ORIFICE
33800
34200
21800
22800
1100
1100
3.61
3.64
10.05
10.05
TXA031C4
TXA035C4
CHG TO 71
FACT INS 71
34200
33800
22800
21800
1100
1100
3.64
3.61
10.05
10.05
TXA049C4
TXA050C4
CHG TO 71
CHG TO 71
36800
36800
26600
26600
1350
1350
3.85
3.85
10.10
10.10
DATA SUBJECT TO CHANGE WITHOUT NOTICE
7A0036A100A
1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER
EQUIPMENT CERTIFICATION PROGRAM, WHICH IS BASED ON A.R.I.
22
STANDARD 210/240.
35
30
2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270.
78
NO
NO
3 CALCULATED IN ACCORDANCE WITH NATL. ELECTRIC CODE. ONLY USE
HACR CIRCUIT BREAKERS OR FUSES.
4 STANDARD AIR - DRY COIL - OUTDOOR
5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT
NAMEPLATE AND SERVICE INSTRUCTION.
6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR -
60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID 60 FT.
FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE
PUB. NO. 12-3312-01.
7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE
AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM
3/8
BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE
SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.
8 NO MEANS NO START COMPONENTS.
7/8
YES MEANS QUICK START KIT COMPONENTS.
3/8
PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.
193
173
CCBB42A4ACC
CUBA36A4ACC
FIXED ORIFICE
FIXED ORIFICE
34200
33800
23800
21800
1200
1100
3.68
3.61
10.05
10.05
TXA036C4
TXA037C4
FACT INS 71
FACT INS 71
35600
35400
24400
24300
1200
1200
3.83
3.73
10.00
10.10
TXC030C4
TXC030D4
CHG TO 71
CHG TO 71
33800
33800
21800
21800
1100
1100
3.61
3.61
10.05
10.05
SPLIT SYSTEM
CUBB36A4ACC
CUBB42A4ACC
FIXED ORIFICE
FIXED ORIFICE
34200
34200
22800
23800
1100
1200
3.64
3.68
10.05
10.05
TXA042C4
TXA043C4
CHG TO 71
CHG TO 71
36000
36200
25100
25900
1250
1350
3.79
3.83
10.15
10.05
TXC031C4
TXC031D4
CHG TO 71
CHG TO 71
34200
34200
22800
22800
1100
1100
3.64
3.64
10.05
10.05
TXA030C4
CHG TO 71
33800
21800
1100
3.61
10.05
TXA048C4
CHG TO 71
36800
26600
1350
3.85
10.10
TXC031E5
TXV-B
35200
23600
1100
3.65
10.40