5-6. RAS-07NKD-E / RAS-07UA-E3
Cooling
0.39m
(Connecting pipe)
∅9.52
O.D.:9.52mm
P
Packed valve
(∅9.52)
Cooling
Cooling Compressor
Cooling
50Hz
Standard
Cooling
Overload
Low temperature
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Indoor unit
Heat exchanger
Cross flow fan
PH80T1-4C
Heat exchanger
Propeller fan
Outdoor unit
Standard
Surface temp. of heat
exchanger interchanging
pressure P
pipe T1 (°C)
(MPaG)
0.45
0.69
0.32
– 23 –
FILE NO. SVM-04022
T1
Packed valve
(∅6.35)
Capillary tube
∅1.5x1200S
Refrigerant
R-22 : 0.57 kg.
Mark(
)means check points of Gas Leak.
Fan speed
(indoor)
13.5
High
18.0
High
2.0
Low
0.49m
(Connecting pipe)
∅6.35
O.D.:6.35mm
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
27/19
35/24
32/23
43/26
21/15
21/15