Noritz ecoTOUGH NRC98-DV Installation Manual page 8

Condensing tankless gas water heater
Hide thumbs Also See for ecoTOUGH NRC98-DV:
Table of Contents

Advertisement

Item
• There must be a clearance of 24" (600mm)
or more in front of the Flue terminal.
• This restriction will not be applied to an
area where an effective shield makes a
clearance of 24" (600mm) or more in
front of the exhaust outlet.
Clearance Requirements from Vent Terminations to Building Openings
* All clearance requirements are in accordance with ANSI Z21.10.3 and the National Fuel Gas Code,
ANSI Z223.1 and in Canada, in accordance with NSCNGPIC.
Maintain the following clearances to any
opening in any building:
For installations in the USA,
• 4' below, 4' horizontally from, or 1'above any
door, operable window, or gravity air inlet into
any building.
3' above any forced air inlet within 10'.
For installations in the Canada,
• 36" (900mm) below, horizontally from, or
above any door, operable window, or gravity
air inlet into any building.
6' (1.8m) from any forced air inlet.
8
Check
<When supplying combustion air from the indoors>
Illustration
There must be no
building opening
within this area.
12" (300mm)
or more
Illustration
4' *
1' *
* Clearances for USA only.
12" (300mm)
or more
Flue terminal
12" (300mm)
or more
12" (300mm)
or more
4' *
3' *