Vent Pipe Installation (When supplying combustion air from the indoors (SV, non-direct vent))
• Disconnect power and turn ON dip switch 3 if combustion air will be
supplied form the indoors as illustrated to the right. Refer to page 29 for
the location of the dip switch bank.
• SV Conversion kit #SV-CK-3 is required for the air intake.
Failure to perform the above 2 steps could result in a ¿ re or explosion causing
property damage, personal injury or death.
Refer to the instructions provided with the conversion kit for additional details.
Horizontal Vent Termination- PVC/CPVC Materials Only
Exhaust
Slope vent
Intake
SV Conversion Kit
Accessory
(#SV-CK-3)
**1' (0.3m) Minimum
Bird screen
90 Elbow
* Not supplied with water
heater, order separately.
**1' (0.3m) Minimum
recommended, but not required.
Pipe Material
Max. Straight Vent Length
No. of Elbows
4" (100mm) Pipe
4
35' (10.8m)
3
41' (12.6m)
2
47' (14.4m)
1
53' (16.2m)
*** Not including the termination.
Vertical Vent Termination- PVC/CPVC Materials Only
Support
Exhaust
Intake
SV Conversion Kit
Accessory
Slope vent
(#SV-CK-3)
Upwards
Bird screen
**1' (0.3m)
Minimum
90 Elbow
* Not supplied with water
**1' (0.3m) minimum
WARNING
Hanger
Straps
Insert Bird
Upwards
Screen* in
Each End
of Tee
PVC or CPVC
***
3" (75mm) Pipe
35' (10.8m)
41' (12.6m)
47' (14.4m)
53' (16.2m)
Insert Bird
Screen* in
End of 45
Elbow
Storm
Collar
Roof
Flashing
Firestop/Support
Firestop
Hanger
Strap
heater, order separately.
recommended, but not required.
A tee, 45 elbow, or the PVT-HL termination may be used
for the vent termination. It is not necessary to use bird
screens with the PVT-HL termination.
Terminate at least 12" (300mm) above grade or above
snow line.
Terminate at least 7' (2.1m) above a public walkway,
6' (1.8m) from the combustion air intake of any appliance,
and 3' (0.9m) from any other building opening, gas utility
meter, service regulator etc.
Terminate at least 3' (0.9m) above any forced air inlet within
10' (3m) , 4' (1.2m) below, 4' (1.2m) horizontallyfrom or
1' (0.3m) above any door, window, or gravity air inlet into any
building per National Fuel Gas Code ANSI Z223.1/NFPA 54.
Slope the horizontal vent 1/4" upwards for every 12" (300mm)
toward the termination.
Use a condensation drain if necessary.
In the Commonwealth of Massachusetts a carbon monoxide
detector is required for all side wall horizontally vented gas
fuel equipment.
Please refer to Technical Bulletin TB 010606 for full installation
in structions.
When installed in a manufactured home, all combustion air
must be supplied from the outdoors as shown on pages 15 - 16.
Terminate at least 6' (1.8m) from the combustion air
intake of any appliance, and 3' (0.9m) from any other
building opening, gas utility meter, service regulator etc.
Enclose exterior vent systems below the roof line to limit
condensation and protect against mechanical failure.
When the vent penetrates a floor or ceiling and is not
running in a fire rated shaft, a firestop and support is
required.
When the vent termination is located not less than
8' (2.4m) from a vertical wall or similar obstruction,
terminate above the roof at least 2' (0.6m), but not
more than 6' (1.87m), in accordance with the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
Provide vertical support every 3' (0.9m) or as required
by the vent pipe manufacturer's instructions.
A short horizontal section is recommended to prevent
debris from falling into the water heater.
When using a horizontal section, slope the horizontal
vent 1/4" upwards for every 12" (300mm) toward the
termination to drain condensate.
When installed in a manufactured home, all combustion air
must be supplied from the outdoors as shown on page 15.
* Dip switch No.3 is turned on.
17