Noritz ecoTOUGH NRC98-DV Installation Manual page 16

Condensing tankless gas water heater
Hide thumbs Also See for ecoTOUGH NRC98-DV:
Table of Contents

Advertisement

Horizontal Vent Termination- 3" (75m) Concentric PVC/CPVC Termination
3" (75mm) or
4" (100mm)
Intake*
3" (75mm) or
4" (100mm)
Exhaust*
* 4" (100mm) pipe requires the use of a reducing coupling
just prior to the termination.
3" (75mm) PVC or CPVC
No. of
Max. Straight Vent Length**
Elbows
4
35' (10.8m)
41' (12.6m)
3
2
47' (14.4m)
1
53' (16.2m)
** Not including the concentric termination
16
Hanger
Straps
Strap
Insert Bird Screen
in End of Termination
Slope vent
Upwards
4" (100mm) PVC or CPVC
Max. Straight Vent Length**
35' (10.8m)
41' (12.6m)
47' (14.4m)
53' (16.2m)
The concentric termination may be shortened,
but not lengthened from its original factory
supplied length.
The concentric termination may only be used
for horizontal terminations.
1" (25mm)
Minimum
3" (75mm) or 4" (100mm) PVC or CPVC pipe
may be used with the concentric termination.
Maintain the same vent pipe diameter from the
water heater flue to the termination.
Do not exceed the maximum vent lengths as
specified in this section.
When using 4" (100mm) pipe, it will be necessary
to use 4" (100mm) x 3" (75mm) reducing couplings
and a short section of 3" (75mm) pipe to connect to
the termination.
Use no more than a 6" (150mm) section of pipe to
make the connection between the reducing
couplings and the termination.
There must be a minimum of 1" (25mm) clearance
between the outside wall and the air intake section
of the termination as illustrated on the left.
Install a securing strap to prevent movement of
the termination.
Terminate at least 12" (300mm) above grade or
above snow line.
Terminate at least 7' (2.1m) above a public walkway,
6' (1.8m) from the combustion air intake of any
appliance, and 3' (0.9m) from any other building
opening, gas utility meter, service regulator etc.
T erminate at least 3' (0.9m) above any forced air
inlet within 10' (3m), 1' (0.3m) below, 1' (0.3m)
horizontally from or 1' (0.3m) above any door,
window, or gravity air inlet into any building per
National Fuel Gas Code ANSI Z223.1/NFPA 54.
Slope the horizontal vent 1/4" upwards for every
12" (300mm).
Use a condensation drain if necessary.
In the Commonwealth of Massachusetts a carbon
monoxide detector is required for all side wall
horizontally vented gas fuel equipment.
Please refer to Technical Bulletin TB 010606 for full
installation in structions.