Mitsubishi Electric PU-P71VHA Service Manual page 56

Split-type heat pump air conditioners
Hide thumbs Also See for PU-P71VHA:
Table of Contents

Advertisement

SW2 setting
Indoor setting temperature
ON
17~30
1
2 3 4 5 6
Outdoor piping temperature/Cond./Eva.
ON
(TH6)
– 39~88
1
2 3 4 5 6
Discharge super heat. SHd
0~255
ON
Cool = TH4-TH6
1
2 3 4 5 6
Heat = TH4-TH5
Sub cool. SC
0~130
ON
Cool = TH6-TH3
1
2 3 4 5 6
Heat = TH5-TH2
Communication demanded capacity.
0~255
ON
1
2 3 4 5 6
When no communication demanded
setting, "100" is displayed.
Error thermistor display
ON
1
2 3 4 5 6
Fan step on error occurring.
ON
0~16
1
2 3 4 5 6
LEV opening on error occurring
0~500
ON
1
2 3 4 5 6
Outdoor piping temperature/Cond./Eva.
on error occurring. (TH6)
ON
– 39~88
1
2 3 4 5 6
Discharge super heat on error occurring.
SHd
ON
0~255
Cool = TH4-TH6
1
2 3 4 5 6
Heat = TH4-TH5
Sub cool on error occurring. SC
0~130
ON
Cool = TH6-TH3
1
2 3 4 5 6
Heat = TH5-TH2
Display detail
When air conditioners are
connected to M-NET and
under central control.
Explanation for display
17~30
– 39~88
(When the temperature is 0: or less, "–" and
temperature are displayed by turns)
0~255
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) 115 :
One second interval.
1
0~130
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
0~255
(When the capacity is 100 or more, the hundreds
digit and tens, units digit are displayed by turns)
(Example) When 100
One second interval.
1
3: Outdoor liquid piping thermistor (TH3)
6: Outdoor condenser thermistor (TH6)
When no error thermistor, "–" is
displayed.
0~16
0~500
– 39~88
(When the thermistor is 0:and less, "–" and
temperature are displayed by turns.)
(Example) When –15:
One second interval
0~255
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 150:
One second interval
1
0~130
(When the temperature is 100 or more, the hundreds
digit and tens, units digit are displayed by turns.)
(Example) When 115:
One second interval
1
56