Cutting/Extending The Piping - Samsung AS12A1VC Owner's Instructions & Installation Manual

Ductless mini-split
Table of Contents

Advertisement

AS12A1VC-E
1/26/00 3:16 PM

Cutting/Extending the Piping

Five metres of piping is supplied with the air conditioner(Optional).
This length can if necessary be:
Extended to a maximum of ten metres
Shortened as required
If more than five metres of piping is required:
The assembly cable must also be extended
Refrigerant must be added to the circuit by an
approved installer; otherwise, the indoor unit may
freeze
1
Make sure that you have the required tools available (pipe cutter, reamer,
flaring tool and pipe holder).
2
If you wish to shorten the piping, cut it using a pipe cutter, taking care to
ensure that the cut edge remains at a 90° angle with the side of the pipe,
and referring to the illustrations below for examples of edges cut correctly
and incorrectly.
O
90
O
3
To prevent any gas from leaking out, remove all burrs at the cut end of the
pipe, using a reamer.
4
Slide a flare nut on to the pipe and modify the flare.
Pipe
Liquid refrigerant
Gas refrigerant
Gas refrigerant
5
Check that the flaring is correct, referring to the illustrations below for
examples of incorrect flaring.
Inclined
Damaged Surface
6
Align the pipes to be connected and tighten the flare nuts first manually
and then with a wrench, applying the following torque.
Pipe
Liquid refrigerant
Gas refrigerant
Gas refrigerant
7
For further details on how to connect up to the outdoor unit and purge the
circuit, refer to page 38.
Page 11
Oblique
Rough
x
x
Outer Diameter (D)
6.35 mm (1/4")
1.3 mm (5/100")
9.52 mm (3/8")
1.8 mm (7/100")
12.70 mm (1/2")
2.0 mm (8/100")
Cracked
Outer Diameter
Torque (kg•cm)
6.35 mm(1/4")
9.52 mm(3/8")
12.70 mm(1/2")
Burr
x
Depth (A)
Uneven Thickness
3
160 (11 ft•lb)
5
3
300 (21 ft•lb)
4
2
500 (36 ft•lb)
5
I
I
U
NSTALLING THE
NDOOR
NIT
33
E-