Once combustion is set to 9.0% press
the 'ip' button.
The display will alternate between the
fan speed ('00' or minimum in this
case) and the boiler temperature.
To select the next fan speed press the
'CH +ve' button.
'33' will be displayed, indicating
ignition speed.
To view the Set Flame value at that fan
speed press the 'ip' button.
The display will alternate between the
ignition fan speed ('33') and the Set
Flame value ('38' in this example).
Change the Set Flame value to achieve
9.0% CO2 by pressing 'CH -ve' or
'CH +ve'.
Press the 'ip' button followed by
'CH +ve' to change to maximum fan
speed ('100'). Press the 'ip' button to
display the Set Flame value. The value
can be changed by pressing 'CH -ve'
or 'CH +ve' buttons to achieve
9.0% CO2.
Once combustion has been checked,
adjusted where necessary, and the
readings recorded at each fan speed
press reset 'R' button to escape the
calibration function - 'ESC' will be
displayed.
To Flue
Sampling Point
To Flue
Sampling Point