Carrier 38TUA Product Data page 11

50 hz air conditioner
Table of Contents

Advertisement

Detailed cooling capacities* (S.I.) continued
EVAP.
AIR
28
Capacity†
Comp.
(kW)
(C)
Power
L/S
EWB
Total Sens‡
kW**
38TUA048-95, 96 Outdoor Section with F(A,B)4(A,B)S(F,B)048 Indoor Section
22
15.5
7.89
4.72
20
14.5
9.31
4.61
650
18
13.6
10.7
4.51
16
12.9
11.8
4.43
14
12.5
12.5
4.39
22
15.8
8.29
4.82
20
14.8
9.90
4.71
750
18
13.9
11.5
4.61
16
13.3
12.6
4.53
14
13.0
13.0
4.51
22
16.1
8.69
4.92
20
15.1
10.5
4.80
850
18
14.2
12.2
4.70
16
13.6
13.3
4.63
14
13.5
13.5
4.63
Indoor
Section
Size
F(A,B)4(A,B)S(F,B)
048
060
38TUA060-95, 96 Outdoor Section With F(A,B)4(A,B)S(F,B)060 Indoor Section
22
19.4
10.0
5.51
20
18.2
12.0
5.39
850
18
17.1
14.0
5.27
16
16.3
15.4
5.19
14
16.0
16.0
5.16
22
19.6
10.4
5.63
20
18.4
12.6
5.50
950
18
17.3
14.7
5.39
16
16.6
16.2
5.31
14
16.5
16.5
5.30
22
19.7
10.6
5.69
20
18.5
12.9
5.56
1000
18
17.4
15.1
5.45
16
16.8
16.5
5.37
14
16.7
16.7
5.37
Indoor
Section
Size
F(A,B)4(A,B)S(F,B)
060
FB4(A,B)SB
070
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI Standard 210/240-94 and connected by 7.62m of
tubing. If other than 7.62m of tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 27°C entering air at the indoor coil. For sensible capacities at other than 27°C, deduct 245 kW per
480 L/S CFM of indoor coil air for each degree below 27°C, or add 235 kW per 480 l/s of indoor coil air per degree above 27°C. When the required
data falls between the published data, interpolation may be performed.
** System kW is total of indoor and outdoor unit kilowatts.
CONDENSER ENTERING AIR TEMPERATURES °C
32
36
Capacity†
Capacity†
Comp.
(kW)
(kW)
Power
Total Sens‡
Total Sens‡
kW**
15.1
7.72
5.02
14.6
7.54
14.1
9.13
4.90
13.7
8.95
13.2
10.5
4.79
12.8
10.3
12.5
11.6
4.71
12.1
11.4
12.2
12.2
4.68
11.9
11.8
15.3
8.12
5.12
14.9
7.94
14.4
9.72
5.00
13.9
9.54
13.5
11.3
4.90
13.1
11.1
12.9
12.4
4.82
12.5
12.1
12.7
12.7
4.80
12.4
12.3
15.6
8.51
5.22
15.1
8.33
14.6
10.3
5.10
14.1
10.1
13.7
12.0
4.99
13.3
11.7
13.2
13.0
4.92
12.8
12.7
13.1
13.1
4.92
12.8
12.8
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Capacity
Power
1.00
1.00
1.03
1.03
18.8
9.81
5.90
18.1
9.59
17.6
11.8
5.77
17.0
11.6
16.6
13.7
5.65
16.0
13.5
15.8
15.1
5.56
15.3
14.9
15.6
15.6
5.54
15.2
15.2
19.0
10.2
6.02
18.3
9.98
17.8
12.4
5.89
17.2
12.2
16.8
14.5
5.77
16.3
14.2
16.1
15.9
5.69
15.6
15.5
16.0
16.0
5.68
15.6
15.6
19.1
10.4
6.08
18.4
10.2
17.9
12.7
5.94
17.3
12.5
16.9
14.8
5.83
16.4
14.5
16.3
16.2
5.76
15.8
15.8
16.2
16.2
5.75
15.8
15.8
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Capacity
Power
1.00
1.00
1.02
1.02
40
Capacity†
Capacity†
Comp.
Comp.
(kW)
(kW)
Power
Power
Total Sens‡
Total Sens‡
kW**
kW**
5.33
14.1
7.36
5.67
13.6
5.21
13.2
8.77
5.54
12.7
5.10
12.4
10.1
5.42
11.9
5.01
11.8
11.2
5.33
11.4
4.98
11.6
11.5
5.30
11.2
5.44
14.3
7.76
5.78
13.8
5.31
13.4
9.35
5.64
12.9
5.20
12.6
10.9
5.52
12.2
5.12
12.1
11.9
5.45
11.7
5.11
12.0
12.0
5.44
11.7
5.54
14.5
8.15
5.87
14.0
5.41
13.6
9.93
5.74
13.1
5.30
12.9
11.4
5.63
12.4
5.23
12.4
12.4
5.56
12.0
5.23
12.4
12.4
5.56
12.0
Indoor
Section
FG3ASA
6.32
17.5
9.36
6.75
16.9
6.18
16.4
11.4
6.60
15.9
6.05
15.5
13.2
6.47
15.0
5.96
14.9
14.6
6.39
14.4
5.94
14.8
14.8
6.37
14.3
6.44
17.7
9.76
6.87
17.0
6.29
16.6
11.9
6.72
16.0
6.17
15.7
13.9
6.60
15.2
6.10
15.2
15.1
6.52
14.7
6.09
15.2
15.2
6.52
14.7
6.49
17.8
9.94
6.93
17.1
6.35
16.7
12.2
6.78
16.1
6.23
15.8
14.1
6.66
15.3
6.16
15.3
15.3
6.59
14.9
6.16
15.3
15.3
6.59
14.9
Indoor
Section
FG3ASA
44
48
Capacity†
Comp.
Comp.
(kW)
Power
Power
Total Sens‡
kW**
kW**
7.18
6.03
13.1
6.99
6.41
8.58
5.89
12.2
8.40
6.26
9.95
5.76
11.5
9.75
6.13
10.9
5.68
11.0
10.7
6.04
11.2
5.66
10.9
10.9
6.03
7.57
6.14
13.3
7.38
6.52
9.16
5.99
12.4
8.97
6.37
10.6
5.87
11.7
10.4
6.25
11.6
5.80
11.3
11.3
6.17
11.6
5.79
11.3
11.3
6.17
7.96
6.23
13.5
7.77
6.62
9.73
6.09
12.6
9.53
6.47
11.2
5.98
12.0
10.9
6.36
12.0
5.92
11.6
11.6
6.30
12.0
5.92
11.6
11.6
6.30
Cooling
Size
Capacity
048
0.97
060
0.99
9.14
7.21
16.2
8.91
7.70
11.1
7.06
15.3
10.9
7.54
13.0
6.93
14.4
12.7
7.41
14.2
6.84
13.9
13.8
7.32
14.3
6.84
13.8
13.8
7.32
9.53
7.33
16.4
9.30
7.82
11.7
7.18
15.4
11.5
7.66
13.5
7.06
14.6
13.2
7.54
14.7
6.99
14.2
14.2
7.48
14.7
6.99
14.2
14.2
7.48
9.72
7.39
16.4
9.49
7.88
12.0
7.24
15.4
11.7
7.72
13.8
7.12
14.8
13.4
7.61
14.9
7.06
14.4
14.4
7.55
14.9
7.06
14.4
14.4
7.55
Cooling
Size
Capacity
060
0.98
52
Capacity†
Comp.
(kW)
Power
Total Sens‡
kW**
12.6
6.81
6.81
11.8
8.21
6.66
11.0
9.55
6.52
10.6
10.5
6.43
10.5
10.5
6.42
12.8
7.20
6.92
11.9
8.78
6.76
11.3
10.1
6.64
10.9
10.9
6.57
10.9
10.9
6.57
12.9
7.58
7.01
12.1
9.34
6.86
11.5
10.6
6.76
11.2
11.2
6.70
11.2
11.2
6.70
Power
1.02
1.02
15.6
8.68
8.21
14.6
10.6
8.04
13.8
12.3
7.91
13.3
13.3
7.82
13.3
13.3
7.82
15.7
9.07
8.33
14.8
11.2
8.16
14.1
12.8
8.05
13.7
13.7
7.98
13.7
13.7
7.98
15.8
9.26
8.39
14.8
11.5
8.22
14.2
13.0
8.11
13.9
13.9
8.06
13.9
13.9
8.06
Power
1.00
11

Advertisement

Table of Contents
loading

Table of Contents