B: Method 3, GPN and GPP only
For the optimum in quiet operation,
attic air may be brought directly to the
furnace.
IMPORTANT: In applications using
Method 3 for combustion air, the attic
must be ventilated by gable or soffit
vents. See Figure 7.
CAUTION
!
COMBUSTION AIR INTAKES
CANNOT BE TERMINATED
OUTSIDE. DOING SO CAN CAUSE
IMPROPER OPERATION OF THE
FURNACE.
FIGURE 10
COMBUSTION AIR FITTING – OPTIONAL ATTIC COMBUSTION AIR PULL, GPN & GPP ONLY
12" MIN. FROM
TOP OF INSULATION
10 FT. MAX.
INCLUDING
HORIZONTAL DIRECTION
#8 SCREW
CAUTION
!
USE OF SHEET METAL
AIR INTAKE PIPE INSTEAD
OF PVC MAY RESULT IN
NOISE ISSUES.
FIGURE 9
OUTSIDE AIR USING A HORIZONTAL INLET & OUTLET
If attic combustion air is used, the inlet
air opening at the furnace must be
protected from accidental blockage.
Install a 90° elbow pointing horizontally
at the top of inlet air pipe. See Figure
10 (maximum of 2, 45° or 90° elbows,
allowed).
NOTE: Maximum length of pipe that
may be used for combustion air is 10
feet with two elbows. Lengths of more
ATTACH A 90° ELBOW TO TOP INLET AIR
OPENING TO PREVENT ACCIDENTAL BLOCKAGE
OF INTAKE OPENING.
PVC
ELBOW
INSULATION
6" MINIMUM
CLEARANCE
PVC
COUPLER
than 10 feet can result in nuisance
pressure switch trips.
EXHAUST
ATTIC SPACE
METAL FLUE PIPE ONLY
INDOOR SPACE
#8 SCREWS