Bryant 352AAV Installation, Start-Up, And Operating Instructions Manual
Bryant 352AAV Installation, Start-Up, And Operating Instructions Manual

Bryant 352AAV Installation, Start-Up, And Operating Instructions Manual

Deluxe 4-way multipoise 2-stage condensing gas furnace
Table of Contents

Advertisement

352AAV
Deluxe 4- -Way Multipoise 2- -Stage
Condensing Gas Furnace
Installation, Start- -Up, and Operating Instructions
Visit www.Bryant.com
NOTE:
Read the entire instruction manual before starting
the installation. Please retain these instructions with the furnace
after installation for future reference.
NOTE: This furnace can be installed as a
or (1-pipe) non-direct vent
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA
B149 code. Vent systems must be composed of pipe, fittings,
cements, and primers listed to ULC S636.
fittings and accessory concentric vent termination kits and
accessory external drain trap have been certified to ULC S636 for
use with those IPEX PVC vent components which have been
certified to this standard. In Canada, the primer and cement must
be of the same manufacturer as the vent system - - IPEX System
636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and
(1)
IPEX System 636
t, PVC Cement for Flue Gas Venting, rated
Class IIA, 65 deg C. must be used with this venting system - - do
not mix primers and cements from one manufacturer with a vent
system from a different manufacturer. Follow the manufacturer's
instructions in the use of primer and cement and never use primer
or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system
is based on following these installation instructions, the vent
system manufacturer's installation instructions, and proper use of
primer and cement. All fire stop and roof flashing used with this
system must be UL listed material. Acceptability under Canadian
standard CSA B149 is dependent upon full compliance with all
installation instructions. Under this standard, it is recommended
that the vent system be checked once a year by qualified service
personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
(1) System 636 is a trademark of IPEX Inc.
for Sizes 060- -120, Series B
(2-pipe) direct vent
condensing gas furnace.
The special vent
Consignes spéciales pour l'installation de ventillation au Canada
L'installation faite au Canada doit se conformer aux exigences du
code CSA B149. Ce systême de ventillation doit se composer de
tuyaux, raccords, ciments et apprêts conformes au ULC S636. La
tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que l'ensemble du drain de condensat
extérieur ont été certifiés ULCS 636 pour l'application des
composantes IPEX PVC qui sont certifiées à ce standard. Au
Canada l'apprêt et le ciment doivent être du même manufacturier
que le systême de ventillation - - IPEX Système 636, Apprêt
PVC/CPVC. Mauve Violette pour conduit en évacuation des gaz
et IPEX Système 636
t, ciment pour PVC pour conduit en
(1)
évacuation des gaz, évalué CLASSE IIA, 65 deg. C. doit ëtre
utilisé avec ce systèeme d'évacuation - - ne pas mélanger l'apprêt
et le ciment d'un manufacturier avec le systême de ventillation
d'un autre manufacturier. Bien suivre les indications du
manufacturier lors de l'utilisation de l'apprêt et du ciment et ne
pas utiliser ceux- -ci si la date d'expiration est atteinte.
L'opération sécuritaire, tel que définit par ULC S636, du système
de ventilation est basé sur les instructions d'installation suivantes,
ainsi que l'usage approprié de l'apprêt et ciment. Tout arrët feu et
solin de toit utilisés avec ce système doivent être des matériaux
listés UL. L'acceptation du standard Canadien CSA B419 est
directement relié à l'installation conforme aux instructions ci- -
haut mentionnées. Le standard Canadien recommande l'
inspection par un personel qualifié et ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs
en bâtiments, département des incendies, etc) devraient être
consultées avant l'installation afin de déterminer si un permis est
requis.
1
ama
ISO 9001:2000
CERTIFIED
REGISTERED

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 352AAV and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bryant 352AAV

  • Page 1 352AAV Deluxe 4- -Way Multipoise 2- -Stage Condensing Gas Furnace Installation, Start- -Up, and Operating Instructions for Sizes 060- -120, Series B Visit www.Bryant.com NOTE: Read the entire instruction manual before starting the installation. Please retain these instructions with the furnace after installation for future reference.
  • Page 2 Required Notice for Massachusetts Installations IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA- -54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Sequence of Operation ......Two-Stage Heating With Single-Stage Thermostat SAFETY CONSIDERATIONS .
  • Page 4 The design of the 352AAV furnace is not CSA maintenance, or use can cause explosion, fire, electrical shock, or certified for installation in mobile homes, recreational vehicles, or other conditions which may cause death, personal injury, or outdoors.
  • Page 5: Codes And Standards

    CODES AND STANDARDS S Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other Follow all national and local codes and standards in addition construction materials. It also prevents the entrainment of to these instructions.
  • Page 6 Dimensions --- IN. (mm) UNIT SIZE 060 --- 12 / 036060 17-1/2 (445) 15-7/8 (403) 16 (406) 080 --- 12 / 036080 17-1/2 (445) 15-7/8 (403) 16 (406) 080 --- 16 / 048080 17-1/2 (445) 15-7/8 (403) 16 (406) 100 --- 16 / 048100 21 (533) 19-3/8 (492) 19-1/2 (495)
  • Page 7: Combustion And Ventilation Air

    335122-201 REV. B LIT TOP A08435 Fig. 3 - - Clearances to Combustibles Step 3 - - Combustion and Ventilation Air Step 6 - - Gas Piping and Gas Pipe Pressure Testing S US: Section 9.3 of the NFPA 54/ANSI Z223.1- -2006, Air for S US: NFPA 54/ANSI Z223.1- -2006;...
  • Page 8: Venting

    Step 8 - - Venting S US: NFPA 54/ANSI Z223.1- -2006 Chapters 12 and 13. The model 352AAV 4-way multipoise, Gas-Fired, Category IV, condensing furnace is available in model sizes ranging from input S CANADA: CAN/CSA- -B149.1- -05 Part 8 and Appendix C capacity of 60,000 to 120,000 Btuh as a direct vent (2-pipe) application as well as a non-direct vent (1-pipe) application.
  • Page 9 FURNACE BLOWER SHELF CONDENSATE DOOR TRAP FURNACE CONDENSATE DOOR FURNACE TRAP (INSIDE) FURNACE SIDE SIDE 124 mm 102 mm 146 mm 146 mm 667 mm 19 mm FIELD FIELD 667 mm DRAIN DRAIN 38 mm CONN CONN ALTERNATE DRAIN TUBE LOCATION SIDE VIEW FRONT VIEW END VIEW...
  • Page 10: Downflow Applications

    PLUG PLUG COLLECTOR BOX COLLECTOR BOX DRAIN TUBE (BLUE DRAIN TUBE (BLUE & WHITE STRIPED) & WHITE STRIPED) COLLECTOR BOX COLLECTOR BOX TUBE (PINK) TUBE (PINK) COLLECTOR BOX COLLECTOR BOX TUBE (GREEN) TUBE (GREEN) COLLECTOR BOX INDUCER HOUSING DRAIN TUBE (BLUE) (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX...
  • Page 11 COLLECTOR BOX DRAIN TUBE (BLUE) PLUG PLUG COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX EXTENSION TUBE COLLECTOR BOX COLLECTOR BOX TUBE (PINK) TUBE (PINK) COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX COLLECTOR BOX DRAIN TUBE (BLUE EXTENSION TUBE &...
  • Page 12: Horizontal Left (Supply-Air Discharge) Applications

    Step 4 - - Horizontal Left (Supply-Air Discharge) d. Use inducer housing drain tube (violet label and factory-supplied in loose parts bag) to connect Applications LOWER inducer housing drain connection to the In a horizontal left furnace application, the blower is located to condensate trap.
  • Page 13: Horizontal Right (Supply-Air Discharge) Applications

    PLUG COLLECTOR BOX AUXILIARY "J" BOX DRAIN TUBE (BLUE AND WHITE STRIPED) CONDENSATE COLLECTOR BOX TRAP TUBE (GREEN) INDUCER HOUSING COLLECTOR DRAIN TUBE (VIOLET) BOX EXTENSION COLLECTOR BOX DRAIN TUBE DRAIN TUBE (BLUE) COLLECTOR BOX EXTENSION TUBE DRAIN TUBE COUPLING COLLECTOR BOX TUBE (PINK) RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR 040, 060, AND 080 HEATING INPUT FURNACES...
  • Page 14 COMBUSTION - AIR INTAKE VENT A 12-IN. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE. ″ (762 mm)MIN WORK AREA ″...
  • Page 15 A 3-IN.(76mm) MINIMUM CLEARANCE VENT TO COMBUSTION-AIR INTAKE IS REQUIRED. COMBUSTION AIR INTAKE A 12-IN. (305mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
  • Page 16: Location

    COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX EXTENSION TUBE PLUG COLLECTOR BOX TUBE (PINK) AUXILARY “J” BOX RELOCATED HERE CONDENSATE TRAP COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) INDUCER HOUSING DRAIN TUBE (VIOLET) COLLECTOR BOX EXTENSION TUBE A01028 Fig.
  • Page 17: Furnace Location Relative To Cooling Equipment

    CAUTION FRONT UNIT DAMAGE HAZARD This gas furnace may be used for construction heat provided that: - -The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace.
  • Page 18: Air For Combustion And Ventilation

    If air is exposed to the following substances, it should not be used for combustion air, and outdoor air may be required for combustion: S Permanent wave solutions S Chlorinated waxes and cleaners S Chlorine based swimming pool chemicals S Water softening chemicals S De-icing salts or chemicals S Carbon tetrachloride S Halogen type refrigerants...
  • Page 19 Table 1 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW) (1 SQ.
  • Page 20 1 SQ IN. PER 4000 CIRCULATING AIR VENT THROUGH ROOF DUCTS DUCTS BTUH* O UTDOORS 12" MAX (305mm) 12 ″ MAX 12 ″ (305mm) (305mm) 1 SQ IN. VENT 1 SQ IN. PER 2000 THR OUGH PER 1000 BTUH* R OOF BTUH* IN DOOR 1 SQ IN .
  • Page 21: Installation

    must not be smaller than 1/4-in. (6 mm) mesh. Louvers and 5/ 16 ″ (8mm) grilles must be constructed so they cannot be closed. (8mm) When combustion air ducts are used, they must be of the same 5/ 16 ″ cross sectional area as the free area of the openings to which they connect.
  • Page 22 FURNACE (OR OTHER MANUFACTURER’S COIL CASING WHEN USED) COMBUSTIBLE PLENUM FLOORING OPENING DOWNFLOW SUBBASE FLOOR SHEET METAL OPENING PLENUM FLOOR OPENING A96283 A07585 Fig. 21 - - Floor and Plenum Opening Dimensions Fig. 22 - - Furnace, Plenum, and Subbase Installed on a Combustible Floor FURNACE APPROVED...
  • Page 23: Ductwork Acoustical Treatment

    Table 3 – Opening Dimensions - - In. (mm) FURNACE PLENUM OPENING FLOOR OPENING CASING APPLICATION WIDTH 24-1/8 16-5/8 24-3/4 Upflow Applications (406) (613) (422) (629) 15-7/8 16-1/2 19-5/8 Downflow Applications on Non-Combustible Flooring (403) (483) (419) (498) 17-1/2 Downflow Applications on Combustible Flooring Using KGASB 15-1/8 16-3/4 20-3/8...
  • Page 24: Return Air Connections

    supply side air duct, humidifier, or other accessories. All communicating with another fuel-burning appliance not of the accessories MUST be connected external to furnace main casing. direct-vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return Downflow Furnaces air plenum on ducts in the closed position.
  • Page 25: Filter Arrangement

    Step 5 - - Filter Arrangement 21-IN. (533mm) WIDE ⁄ -IN. (444mm) WIDE CASINGS ONLY: WARNING CASINGS ONLY: SUPPORT RODS (3) INSTALL FIELD-SUPPLIED EXTEND 1/4" (6mm) ON FILTER FILLER STRIP EACH SIDE OF FILTER AND UNDER FILTER. REST ON CASING FLANGE FIRE, CARBON MONOXIDE AND POISONING HAZARD Failure to follow this warning could result in fire, personal...
  • Page 26: Bottom Closure Panel

    Risers must be used to connect to furnace and to meter. Support CAUTION all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. (2 M). Joint compound (pipe CUT HAZARD dope) should be applied sparingly and only to male threads of joints.
  • Page 27: Electrical Connections

    Table 6 – Electrical Data MAX FUSE OPERATING VOLTAGE VOLTS- MAX WIRE UNIT OR CKT RANGE HERTZ- UNIT WIRE LENGTH UNIT SIZE AMPACITY† PHASE AMPS SIZE FT (M)‡ Max* Min* AMPS** 060–12 / 036060 115---60---1 11.3 33 (10.0) 080–12 / 036080 115---60---1 10.8 34 (10.3)
  • Page 28 FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING 1-STAGE THERMOSTAT TERMINALS FIVE FIELD-SUPPLIED WIRE FUSED DISCONNECT TWO-WIRE 208/230- OR HEATING- 460-V ONLY THREE PHASE 208/230-V W/W1 SINGLE PHASE Y/Y2 115-V FUSED JUNCTION DISCONNECT SWITCH CONTROL CONDENSING (WHEN REQUIRED)
  • Page 29: 24-V Wiring

    FACTORY INSTALLED ELECTRIC LOCATION DISCONNECT SWITCH COPPER WIRE ONLY POWER ENTRY HOLE FILLER PLUG (FACTORY- UNUSED 7/8-IN. (22 mm) SUPPLIED LOOSE PARTS BAG) DIAMETER POWER ENTRY HOLES ALUMINUM WIRE A93033 A05113 Fig. 33 - - Disconnect Switch and Furnace Fig. 34 - - Factory Installed J-Box Location Use a separate, fused branch electrical circuit containing a 24-V WIRING properly sized fuse or circuit breaker for this furnace.
  • Page 30: Removal Of Existing Furnaces From Common Vent Systems

    NFGC or NSCNGPIC. restriction, leakage, corrosion and other deficiencies, The 352AAV can be vented as either a direct vent (all sizes) or as which could cause an unsafe condition. a non-direct vent (except for 140 size) application. A direct vent 3.
  • Page 31 A02176 Fig. 36 - - Wiring Diagram...
  • Page 32 Table 7 – Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (USA only*) ASTM SPECIFICATION SOLVENT CEMENT MATERIAL PIPE FITTINGS DESCRIPTION (MARKED ON AND PRIMERS MATERIAL) D1527 Pipe --- --- --- --- Schedule---40 D1785 Pipe --- --- --- --- Schedule---40 D2235 For ABS...
  • Page 33 SETUP SWITCHES TWINNING AND/OR LOW-HEAT ONLY AND COMPONENT TEST BLOWER OFF-DELAY TERMINAL ACRDJ - AIR CONDITIONING RELAY DISABLE JUMPER 24-V-THERMOSTAT TERMINALS TEST/TWIN TRANSFORMER 24-VAC CONNECTIONS 0.5-AMP024 VAC HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) PL1 - LOW VOLTAGE MAIN FUSE 3-AMP HARNESS CONNECTOR 3-AMP FUSE SEC-1...
  • Page 34 12 inches (30 cm) for applieances >10,000 Btuh(3 kW) and < 100,000 Btuh(30kW), 36 inches (91cm) for appliances > 100,000 Btuh(30kW) A08600 Table 8 – Direct Vent Termination Clearance...
  • Page 35 A08601 Table 9 – Other than Direct Vent Termination Clearance...
  • Page 36 Table 10 – Maximum Allowable Exposed Vent Pipe Length With and Without Insulation in Winter Design Temperature Ambient* MAX PIPE WITHOUT WITH 3/8–IN. (10 mm) OR WINTER DESIGN UNIT SIZE DIAMETER INSULATION THICKER INSULATION TEMPERATURE °F (°C) IN. (mm) FT (M) FT (M)†...
  • Page 37 Table 11 – Furnace Setup Switch Description SETUP SWITCH NO. SWITCH NAME NORMAL POSITION DESCRIPTION OF USE When off, allows 2-stage operation with a single-stage Adaptive Heat thermostat. Turn on when using 2-stage thermostat to allow Low SW---1 Mode Heat operation when R to W/W1 closes and High Heat operation when R to W/W1 and W2 close.
  • Page 38 Table 13 – Maximum Allowable Pipe Length - - Ft. (M) NON-DIRE CT VENT UNIT MAX NUMBER OF 90° ELBOWS DIRECT VENT (2-PIPE) (1-PIPE) ALTITUDE INPUT ONLY ONLY RATE FT (M) (BTUH) TERMINATI PIPE DIA PIPE DIA ON TYPE IN. (MM)* IN.
  • Page 39 Table 13—Maximum Allowable Pipe Length - - Ft. (M) (Continued) NON-DIRE CT VENT UNIT MAX DIRECT VENT (2-PIPE) ONLY NUMBER OF 90° ELBOWS (1-PIPE) ALTITUDE INPUT ONLY FT (M) RATE (BTUH) TERMINATION PIPE DIA PIPE DIA TYPE (IN.)* (IN.)* 1---1/2 (38) 1---1/2 (38) 2 Pipe or 2-in.
  • Page 40 Table 13—Maximum Allowable Pipe Length - - Ft. (M) (Continued) NON-DIRE DIRECT VENT (2-PIPE) CT VENT NUMBER OF 90° ELBOWS ONLY (1-PIPE) ALTITUDE UNIT SIZE ONLY FT (M) (BTUH) TERMINATIO PIPE DIA PIPE DIA N TYPE (IN.)* (IN.)* 1---1/2 (38) 1---1/2 (38) 2 Pipe or 2-in.
  • Page 41 5. Be certain that mating surfaces of inducer housing 4. Chamfer outside edge of pipe for better distribution of connection elastomeric (rubber) coupling, and 2-in. (51 primer and cement. mm) diameter vent pipe are clean and dry. Assemble the 5. Clean and dry all surfaces to be joined. elastomeric (rubber) vent coupling (with 2 loose clamps) 6.
  • Page 42 EXAMPLE: An 080- -12 size furnace located in Indianapolis, elevation 650 ft (198 M) above sea level, could be installed as either a FURNACE direct vent/2-pipe system that requires 3 elbows and 32 ft (10 M) of vent pipe, along with 5 elbows and 34 ft (10 M) of combustion-air pipe OR a non-direct vent/1-pipe system that requires 3 elbows and 32 ft (10 M) vent pipe.
  • Page 43: Vent Termination

    12 ″ MIN (305mm) 12 ″ MIN (305mm) VENT PIPE VENT PIPE COMBUSTION-AIR PIPE COMBUSTION-AIR PIPE HORIZONTAL TO ROOF HORIZONTAL TO SIDEWALL COMBUSTION-AIR PIPE VENT PIPE COMBUSTION-AIR PIPE 12 ″ MIN (304.8mm) 12 ″ MIN VENT PIPE (304.8mm) VERTICAL TO ROOF VERTICAL TO SIDEWALL NOTE: A 12-in.
  • Page 44 Table 14 – Vent Termination Kit for Direct Vent/2-Pipe System DIAM. OF COMBUSTION AIR AND VENT DIRECT VENT (2-PIPE) TERMINATION KIT TERMINATION SYSTEM PIPES --- IN (mm) 2-in. (51 mm) Concentric Vent Kit Single Penetration of Wall or Roof 1, 1---1/2, 2, or 2---1/2 (25, 38, 51, 64 mm) 3-in.
  • Page 45: Condensate Drain

    Combustion air and vent pipes MUST terminate outside structure. (Direct Vent/2-Pipe System ONLY) - - When 2 or more 352AAV A factory accessory termination kit must be installed as shown in furnaces are vented near each other, 2 vent terminations may be Table 14.
  • Page 46: Condensation Drain Protection

    CONDENSATE TRAP OPEN STAND PIPE FOR A/C OR WIRE TIE(S) HUMIDIFIER DRAIN TO OPEN HEAT TAPE DRAIN (3 WRAPS MINIMUM) A94054 Fig. 46 - - Example of Field Drain Attachment A93036 Condensate Trap Heat Tape Fig. 47 - - WARNING Step 1 - - General The furnace must have a 115-v power supply properly connected PERSONAL INJURY HAZARD...
  • Page 47: Prime Condensate Trap With Water

    CAUTION FIRE HAZARD Failure to follow this caution may result in intermittent unit operation or performance satisfaction. This furnace is equipped with a manual reset limit switch in the burner box area. The switch will open and shut off power to the gas valve if a flame rollout or overheating condition occurs in the burner enclosure area.
  • Page 48: Two-Stage Heating With Single-Stage Thermostat (Adaptive Mode)

    CPU, transformer TRAN, inducer motor IDM, blower motor control CPU will repeat the ignition sequence for up to BLWM, hot surface igniter HSI, and gas valve GV. three more Trials-For-Ignition before going Ignition-Lockout. Lockout will be reset automatically TWO-STAGE HEATING WITH SINGLE-STAGE after three hours, by momentarily interrupting 115 vac THERMOSTAT (ADAPTIVE MODE) power to the furnace, or by interrupting 24 vac power at...
  • Page 49: Cooling Mode

    will switch to HI HEAT speed five seconds after the R to G-and-Y1-and-Y/Y2 circuits switch the furnace blower W2 circuit closes. motor BLWM to COOL speed. 2. Switching From High-To Low-Heat - - If the thermostat R NOTE: When transitioning from low-cooling to high-cooling the to W2 circuit opens, and the R to W1 circuit remains outdoor unit compressor will shutdown for 1 minute while the closed, the furnace control CPU will switch the inducer...
  • Page 50 A00275 A00277 Fig. 50 - - Two- -Stage Furnace with Single- -Speed Fig. 52 - - Two- -Stage Furnace with Single- -Speed Air Conditioner Heat Pump (Dual Fuel) A00276 A00278 Fig. 51 - - Two- -Stage Furnace with Two- -Speed Fig.
  • Page 51 A00279 A00281 Fig. 54 - - Dual Fuel Thermostat with Two- -Stage Furnace and Fig. 56 - - Two- -Stage Thermostat with Two- -Stage Furnace Single- -Speed Heat Pump and Two- -Speed Air Conditioner See note 2 A00280 A00282 Fig. 55 - - Dual Fuel Thermostat with Two- -Stage Furnace and Fig.
  • Page 52 NOTES FOR FIG. 50- -57: 1. Heat pump MUST have a high pressure switch for dual fuel applications. 2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure. 3. Select the “ZONE” position on the two-speed heat pump control. 4.
  • Page 53: Continuous Blower Mode

    b. When the R to G-and Y/Y2 circuit is closed and there on for the selected blower-OFF delay period. If the R-to is a demand for dehumidification, the furnace blower W/W1-and-Y1 signals disappear, leaving the G signal, the blower motor BLWM will drop the blower speed from COOL motor BLWM will remain on for the selected blower-OFF to HI HEAT for a maximum of 10 minutes before delay period then switch to continuous-blower speed.
  • Page 54: Operate Furnace

    Move setup switch SW-1 to OFF position after c. Verify furnace model and size. Table 15 can only be completing low-heat adjustment. used for model 352AAV furnaces with heating inputs g. Jumper R and W1 and W2 thermostat connections on of 20,000/13,000 (High/Low) Btuh per burner.
  • Page 55 Table 15 – Model 352AAV Orifice Size and High/Low-Heat Manifold Pressures for Correct Inputs for Use with 060 Through 120 Size Furnaces Only (Tabulated Data Based on 20,000/13,000 Btuh per Burner, Derated 2 Percent for Each 1000 ft (305 M)Above Sea Level)*...
  • Page 56 Table 15 - - Model 352AAV Orifice Size and High/Low-Heat Manifold Pressures for Correct Inputs (Continued) for Use With 060 Through 120 Size Furnaces Only (Tabulated Data Based on 20,000/13,000 Btuh per Burner, Derated 2 Percent for Each 1000 ft (305 M) Above Sea Level)*...
  • Page 57 Table 15 - - Model 352AAV Orifice Size and High/Low-Heat Manifold Pressures for Correct Inputs (Continued) for Use With 060 Through 120 Size Furnaces Only (Tabulated Data Based on 20,000/13,000 Btuh per Burner, Derated 2 Percent for Each 1000 ft (305 M) Above Sea Level)*...
  • Page 58 NOTE: Be sure all pressure tubing, combustion-air and vent LOW-FIRE ON/OFF pipes, and burner enclosure front are in place when checking ADJUSTMENT SWITCH ALLEN SCREW input by clocking gas meter. (UNDER CAP) a. Calculate high-altitude adjustment (if required). HIGH-FIRE UNITED STATES ADJUSTMENT At altitudes above 2000 ft, this furnace has been ALLEN SCREW...
  • Page 59: Set Temperature Rise

    Table 16 – Altitude Derate Multiplier for USA. SET TEMPERATURE RISE ALTITUDE PERCENT OF DERATE MULTIPLIER CAUTION FT (M) DERATE FACTOR* 0–2000 1.00 (0 --- 610) UNIT DAMAGE HAZARD 2001–3000 4---6 0.95 Failure to follow this caution may result in overheating the (610 --- 914) heat exchangers or condensing flue gases in heat exchanger 3001–4000...
  • Page 60: Adjust Blower Off Delay (Heat Mode)

    Step 6 - - Check Safety Controls CAUTION This section covers the safety controls that must be checked before the installation is complete. The flame sensor, gas valve, UNIT DAMAGE HAZARD and pressure switch were all checked in the Start-up procedure Failure to follow this caution may result in damage to the heat section as part of normal operation.
  • Page 61: Checklist

    CHECKLIST 1. Put away tools and instruments. Clean up debris. 5. Cycle test furnace with room thermostat. 2. Check SW-1 through SW-3 after completing installation to 6. Check operation of accessories per manufacturer’s ensure desired settings for thermostat type (SW-1) and instructions.
  • Page 62 ____________ Pressure Switch Catalog No. II352A --- 60 --- 2 E2008 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 12/08 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Table of Contents

Save PDF