STS32/STS32H Touchscreen Programmable Thermostat
Table 3. Installer Setup Menu. (CONTINUED)
Installer
Installer
Setup
Setup
Settings
Number
Name
1- Highest energy savings.
Temperature
2- Moderate energy savings.
0690
Control in Cool
3- Least energy savings.
-3°F (-1.5°C)
-2°F (-1°C)
-1°F (-.5°C)
0°F (0°C)(no difference in displayed
Temperature
0700
temperature and actual room
Display Offset
temperature )
1°F (.5°C)
2°F (1°C)
3°F (1.5°C)
0-no thermostat reset.
Reset
1-resets all Installer Setup Options to
0710
Thermostat
default values and resets schedule to
default setting.
Initial
Setting
Notes
Record
Default setting is # 1
Factory Accuracy ±1°F
Purpose of Offset:
1-Components may change value
overtime or compensate for internal
component values changes.
2-Compensate for air flow conditions
Use a reliable independent
thermometer and record room
temperature. Use offset to have
thermostat temperature match
independent reading
Only calendar settings and time are
retained.
58
STS32/STS32H Touchscreen Programmable Thermostat

INSTALLER SYSTEM TEST

Use the Installer System Test to test the W1 W2 E AUX Y1 Y2 and L terminals.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test.
Avoid cycling compressor quickly.

How to Use the Installer System Test

The Installer Test is part of the Installer Setup Menu.
1. Enter the Installer System Test by entering the Installer Setup.
2. Note that the test appears at the end of the Installer Setup Numbers.
3. See Fig. 30 to review how the thermostat buttons are used during the Installer System
Test. See table 4 (pg 61) for available Installer System Tests.