Boiler Location & Clearances - Worcester GREENSTAR 25Si Instruction Manual

Wall hung rsf gas fired condensing combination boiler
Table of Contents

Advertisement

SERVICING CLEARANCES
VENTED COMPARTMENT
Using 100mm flue kit
1080mm
Using 125mm flue kit
1450mm
- 1110mm
VENTILATION FREE COMPARTMENTS
INSTALLATION CLEARANCES
Ventilation Free Compartment Installation Clearances
The suggested total unventilated compartment minimum clearances are:
Side
400mm
170mm approx.
(30mm above
the elbow)
(Note: Top and bottom clearances must not be reduced below these values as they are the
minimum required for servicing).
If total side clearance is
reduced to:
**
350mm
300mm
250mm
200mm
150mm
100mm
50mm
If front clearance (to
removable door) is
reduced to:
50mm
25mm
14
BOILER LOCATION & CLEARANCES
930mm
5mm
25mm
to removable door
600mm
front clearance
for service
Above
Below
200mm
If Side Clearances are Reduced
Then overall height clearances
must be increased to (approx):
*
441mm
523mm
617mm
727mm
856mm
1012mm
1202mm
If Front Clearance is Reduced
Then overall height clearances
must be increased to (approx):
*
511mm
596mm
410mm
+ 30mm
above elbow
5mm
200mm
Front (to removable door)
100mm
Front clearance (to removable
OR
door) must be increased to:
129mm
161mm
200mm
243mm
295mm
358mm
434mm
Total side clearance must be
OR
increased to:
**
505mm
569mm
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 25Si/30Si
BOILER LOCATION &
CLEARANCES
This boiler is only suitable for installing internally
within a property at a suitable location onto a
fixed, rigid surface at least the same size as the
boiler and capable of supporting the boiler
weight.
COMPARTMENTS:
Follow the requirements of BS6798 and
BS5440 Part 2 and note:
• Minimum clearances must be maintained
• An access door is required to install, service
and maintain the boiler and any ancilliary
equipment.
• If fitting the boiler into an airing cupboard
use a non-combustible perforated material
(maximum hole sizes of 13mm) to separate
the boiler from the airing space.
BOILER CLEARANCES:
The diagram opposite shows the minimum
space required to install and service the boiler.
If a boiler is installed in a compartment with
clearances less than shown in the tables oppo-
site, ventilation is required. Refer to tables
below for ventilation requirements.
25 & 30 kW
Vent
To room or
position
internal space
High
Minimum free
2
level
area 122 cm
Low
Minimum free
2
level
area 122 cm
BOILER CLEARANCES - UNVENTILATED
COMPARTMENTS:
The tables opposite show the options for the
minimum space required to install and service
the boiler inside an unventilated compartment.
*
NOTE: These are the combined top & bottom
clearances excluding the appliance.
**
NOTE: These are the combined left & right
clearances excluding the appliance.
8 716 115 165a (06/2008)
Direct to
outside
Minimum
free area
2
61 cm
Minimum
free area
2
61cm