10-018 C3082-3682
2/15/10

1-5. Additional Materials Required for Installation

1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire
(See local codes.)
3.
Putty
4.
Refrigeration lubricant
5.
Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

WARNING
AVOID:
direct sunlight.
nearby heat sources that may affect performance of the unit.
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
select a location that will hold the weight of the unit.
select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 2)
install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within the maximum tub-
ing length (L) from the outdoor unit as detailed in Table 3 and
Fig. 3a.
install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television,
radio, telephone, security system, or intercom. Electrical noise
from any of these sources may affect operation.
Table 3
Charge-less Tubing
Model
Length (Actual Length)
KS3082
10 to 100
KS3682
* If total tubing length becomes 100 to 165 ft. (Max.), charge additional refrigerant (R410A) by 0.43 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
11:50 AM
Page 4
To prevent abnormal heat genera-
tion and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or surround-
ing the air conditioner in a way
that may block air flow.
Maximum Tubing
Length (L)
(ft.)
(ft.)
165
Indoor unit
Outside drainage
2" (5 cm)
min.
INDOOR
UNIT
Elevation
difference (H)
CAUTION
For stable operation of the
air conditioner, do not
install wall-mounted type
indoor units less than 5'
(1.5 m) from floor level.
Maximum Elevation Difference (H)
(ft.)
If the outdoor unit is higher
100
If the outdoor unit is lower
50
4
Drain hose
Fig. 1
3" (7.5 cm)
2" (5 cm)
min.
min.
Front View
Fig. 2
Tubing length (L)
OUTDOOR
UNIT
Fig. 3a
Indoor unit
Wall
Minimum height
from floor level
5' (1.5 m)
Floor level
Fig. 3b
Required Amount
of Additional Refrigerant
(oz./ft.)*
0.43