Frame Fastening Method; Drain Hose - Sanyo KS3082 Installation Instructions Manual

Inverter split system air conditioner
Hide thumbs Also See for KS3082:
Table of Contents

Advertisement

10-018 C3082-3682
2/15/10
To unmount indoor unit
Press the 2
marks on the lower part of the indoor unit
and unlatch the tabs. Then lift the indoor unit and
unmount. (Fig. 42)

3-10. Frame Fastening Method

(1) Remove the screw cover on the bottom surface.
(Fig. 43)
(2) Fasten the frame to the rear panel using the 2 sup-
plied tapping screws 5/32" x 13/32" (4 x 10 mm).
(Fig. 43)
NOTE
Under normal conditions, the installation design calls for
a less than 3/32" (2 mm) gap between the air conditioner
unit and the wall.
Confirm that the gap is appropriate (less than 2 mm).

3-11. Drain Hose

a) The drain hose should be slanted downward to the
outdoors. (Fig. 44)
b) Never form a trap in the course of the hose.
c)
If the drain hose will run in the room, insulate the
hose with insulation* so that chilled condensation
will not damage furniture or floors. (Fig. 45)
* Foamed polyethylene or its equivalent is recom-
mended.
WARNING
Risk of Electric Shock
11:50 AM
Page 21
Do not supply power to the
unit or operate it until all
tubing and wiring to the out-
side unit are completed.
Screw
cover
Indoor
unit
Insulation material
(Locally purchased)
must be used.
21
Push
Fig. 42
Screw
Fig. 43
Slant
Drain
hose
Fig. 44
Condensation
Fig. 45