Brilix XHP 40 Installation And User Manual page 15

Swimming pool heat pump xhp
Table of Contents

Advertisement

Parameter 0
setting the temperature for the
incoming water in cooling mode 8 to
35°C, (default setting is 28°C)
Parameter 3
conditions for activating the
defrosting function -30 to 0°C,
(default setting is -7°C)
Parameter 6
mode 0: cooling, 1: heating and
cooling, 2: heating and cooling
and auxiliary heating, 3: heating,
(default setting 3 heating)
Parameter 1
setting the temperature for the
incoming water in heating mode 15 to
40°C, (default setting is 28°C)
Parameter 4
conditions for deactivating the
defrosting function 2 to 30°C,
(default setting is 20°C)
Parameter 7
selecting the electronic
expansion valve mode 0 and 1,
(default setting 1 – automatic)
15
Parameter 2
total operating time for the compres-
sor after defrosting 30 to 90 minutes,
(default setting is 40 minutes)
Parameter 5
defrosting function deactivation
time 1 – 12 minutes,
(default setting is 8 minutes)
Parameter 8
heat target for super performance
in the range of -15 to 15°C,
(default setting 3°C)
EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents