Ras-18Skhp-Es / Ras-18S2Ah-Es - Toshiba RAS-18SKHP-ES Service Manual

Split wall type
Table of Contents

Advertisement

5-3. RAS-18SKHP-ES / RAS-18S2AH-ES

Cooling
0.39 m
Heating
(Connecting pipe)
Æ12.7
P
O.D.:12.7 mm
Packed valve
(Æ12.7)
Heating
Cooling
4-way valve
Heating Cooling
Discharge Muffler
∅25x160L
Cooling
Heating
50Hz
Standard
Heating
Overload*1
Low temperature
Standard
Cooling
Overload
Low temperature
Note
·
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1
·
During heating overload operation, a value for the high temperature limit control operation is included.
Indoor unit
Heat exchanger
Cross flow fan
Compressor
PA200X2CS-4KU1
Accumulator
Heat exchanger
Propeller fan
Outdoor unit
Standard
pressure P
exchanger interchanging
(MPaG)
2.53
3.30 ~ 3.65
1.75
0.54
1.12
0.72
- 15 -
T1
Packed valve
Capillary tube
Æ1.7 x 600
l
Refrigerant
R410A : 1.53 kg.
Mark (
) means check points of Gas Leak.
Surface temp. of heat
Fan speed
pipe T1 (°C)
44.0
51.0 ~ 55.0
32.0
11.0
15.0
4.2
FILE NO. SVM-09036
0.49 m
(Connecting pipe)
Æ6.35
O.D.:6.35 mm
(Æ6.35)
Capillary tube
Æ2.0 x 1000
l
Ambient temp.
conditions DB/WB
(°C)
(indoor)
Indoor
Outdoor
High
20/15
7/6
Low
27/-
24/18
High
20/
-
-10/-10
High
27/19
35/24
High
32/23
43/26
Low
21/15
21/15