Configurable I/O Port Assignments (Sw 7.03.06) - Bosch 560 DDC Quick Start Manual

Direct digital control (ddc) controller
Table of Contents

Advertisement

Quick Start Guide

CONFIGURABLE I/O PORT ASSIGNMENTS (SW 7.03.06)

PORT
Digital Input Enable
Humidity Sensor (0-5V output)
IN-1
CO2 Sensor (0-5V output)
Static Pressure Sensor (0-5V output)
Humidity Sensor (0-5V output)
IN-2
Remote Temperature Sensor (OA or Zone)
IN-3*
Leaving Water Temperature Sensor
IN-4*
UPM Input
Filter Switch
Economizer Cooling (Entering Water Temperature Sensor)
Differential Pressure Switch
Secondary Condensate Pan
Boilerless (Entering Water Temperature Sensor)
EXPANSION PORT 1 (A)
IN-5
Dirty Filter Switch
Smoke Detector Switch
Dirty Filter Switch
Smoke Detector Switch
Dirty Filter Switch
Smoke Detector Switch
IN-6*
Discharge Air Temperature
DO-1*
Fan
DO-2*
Reversing Valve
DO-3*
Compressor Stage 1
DO-4*
Compressor Stage 2
Hot Gas Re-Heat (On/Off)
Fresh Air Damper (On/Off)
Heating Stage 1 (Aux Heat)
DO-5**
Boilerless Control (Aux Heat)
Economizer Cooling
Condenser Water Valve
Variable Frequency Drive (Blower) ABB Drive or Equivalent
AO-1
Mix Air Temperature SCR
AO-2
Modulating Hot Gas Re-Heat Valve
AO-3
Modulating Outside Air Damper
* Non-configurable, factory assigned I/O parameters
** Only one of six possible combinations per application
Quick Start Guide
INPUT PORTS
INPUT EXPANSION MODULE (IEM) COMBINATIONS**
EXPANSION PORT 2 (B)
Fan Status Switch
Fan Status Switch
Fan Status Switch
Fan Status Switch
Fan Status Switch
Fan Status Switch
DIGITAL OUTPUTS
ANALOG OUTPUTS (FHP 583 only)
Subject to change without prior notice
Configurable I/O Port Assignments
EXPANSION PORT 3 (C)
Valve End Switch
Valve End Switch
Differential Pressure Switch
Dirty Filter Switch
Damper End Switch
Secondary Drain Pan
| 13
8733914716 DDC (2014/02)