When The Vertical Louver Does Not Operate - LG A2UN186FA0 Service Manual

Inverter multi type room air conditioner
Table of Contents

Advertisement

When the vertical louver does not operate.

Trouble 5
• Confirm that the vertical louver is normally geared with the shaft of Stepping Motor.
• If the regular torque is detected when rotating the vertical louver with hands ⇒ Normal
• Check the connecting condition of CN-U/D Connector
• Check the soldering condition(on PCB) of CN-U/D Connector
• Confirm that there is DC +12V between pin
• Confirm that there is a soldering short at following terminals.
- Between
,
1
- Between
,
4
• Confirm the assembly condition that are catching and interfering parts in the link of the
vertical louver
Check the operating circuit of the vertical louver
,
and
of MICOM
2
3
4
,
and
of IC01M
5
6
7
If there are no problems after above checks.
of CN-U/D and GND.
- Between
,
,
and
17
18
19
- Between
,
,
and
5
6
7
-95-
of MICOM
20
of IC01M
8