Air Supply And Ventilation - andrews 32/143 Installation Manual, Operation And Service Manual

Hi-flo and standart range natural gas fired storage water heaters
Table of Contents

Advertisement

SECTION 3
AIR SUPPLY
AND
VENTILATION
12
INSTALLATION
Minimum Heights from Roof to Base of Flue Terminal
Type of Roof
Pitch
exceeding
45º
Pitched
Pitch not
exceeding
45º
With
parapet
Flat
Without
parapet
For all installations, please refer to the table below for calculating requirements. Detailed
recommendations for the air supply are given in BS 5440 Part 2, BS 6644 Clause 19
and IGE/UP/10 Pt.1.
The following notes are provided for general guidance only.
Ventilation shall prevent the heater environment from exceeding 32ºC (90ºF).
The purpose provided space in which the heater(s) are installed must have permanent air vents
communicating directly with the outside air, at high and low level. Where communication with the
outside air is possible only by means of high level air vents, ducting down to floor level for the lower
vents must be used.
For an exposed building, air vents must be fitted on at least two sides, preferably on all four sides.
Air vents should have negligible resistance and must not be sited in any position where they are likely
to- be easily blocked or flooded, or in any position adjacent to an extraction system which is carrying
flammable vapour.
Grilles or louvers should be so designed that high velocity air streams do not occur within the space
housing the heater(s).
The grilles should have a total minimum free area for the water heater(s) in addition to any other
requirements as follows:-
Where the heater is to be installed in a room the following permanent
ventilation is required:
5cm
2
per kW in excess of 7kW net for installations up to 54kW net.
For installations exceeding 60kW the following permanent ventilation is required:
540cm
Low Level (inlet)
2
High Level (outlet) 270cm
2
Where the heater is to be installed in a compartment, permanent air vents are required in the
compartment at high and low level. These air vents must either communicate with a room or
internal space or be direct to outside air.
The minimum effective areas of the permanent air vents required in the
compartment are as follows;-
Position of Air Vents
Air from room or internal space
High Level
Low Level
Note:- Both air vents must communicate with the same room or internal space or must both be on the
same wall to outside air.
Not within 1.5m (5ft) of a
vertical surface of a
structure
on the roof
Internal Route
External
Route
On Ridge
Not on Ridge
1m (3.3 ft)
1m (3.3 ft)
above roof
above roof
At or
intersection
intersection
above
ridge
600 mm
level
(24 in)
above roof
The base of
the terminal
intersection
should be
600 mm
600 mm
(2 ft)
(24 in)
above roof
above the
Not
intersection
level of the
applicable
adjacent
250 mm
roof edge
(10 in)
above roof
intersection
plus 5cm
per kilowatt in excess of 54kW total net input.
2
plus 2.5cm
2
per kilowatt in excess of 54kW total net input.
Air Vent Areas
10cm
2
per kW net
20cm
2
per kW net
Within 1.5m (5ft) of a
vertical surface of a
structure
on the roof
Internal
External
Route
Route
The base of the
terminal should
be 600 mm
(24 in) above
the level of
the top of the
structure
Air direct from outside
5cm
2
per kW net
10cm
2
per kW net

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents