8.7 Heating mode
8.7.1 Indoor fan action:
1)
Anti-cold-wind function.
2)
If the compressor stops caused by room temperature rising, indoor fan will be forced to run 127
seconds with breeze. During this period, anti-cold-wind is disabled. After this, anti-cold –wind function is
available.
3)
If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and
anti-cold-wind is disabled.
8.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential.
Auto fan action in heating mode.
8.7.3
After start the operation frequency of compressor submits to following rule:
When the machine runs, if ∆Th stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Zone B: Keep the current frequency.
Zone C: Descend the current frequency one grade.