Vaporstream Models Vlc And Vldi - VAPORSTREAM VLC Installation Instructions And Maintenance Operations Manual

Electric steam humidifiers
Table of Contents

Advertisement

VAPORSTREAM
Dispersion Tube
Thermal Cut-Out
Raised Heater
®
VAPOR-LOGIC
Probes
®
Models VLC AND VLDI
Duct
Cover
Cover Knobs
Evaporating Chamber
Skimmer Port Outlet
Fill Valve
Needle Valve
Manual or Electric
Drain Valve
Clean-out Tray
Control Cabinet
Cover Knobs
Cover
3/4" Overflow
Low-Water Cut-Off
3/4" SST Drain Valve
VAPORSTREAM VLC
Electric Humidifier
State-of-the-art technology in a
simple, low-maintenance humidi-
fier.
This humidifier is designed to be
used with either softened or
unsoftened water (preferably
softened). The probe-type level
control system requires water
conductivity of 100 µS/cm
(34 mg/l) minimum to function,
and therefore will not operate on
water treated by reverse osmo-
sis or deionization. However,
VAPORSTREAM Model VLC
humidifiers are available for use
with these water types. The
standard humidifier can be
converted in the field to a VLDI
model. See below.
OM-628
VAPORSTREAM VLDI
Option
For use with deionized or
reverse osmosis water. This unit
produces chemical-free steam
and reliable, accurate humidifica-
tion control. It is virtually mainte-
nance-free with no wasted
water, no wasted heat, and very
little or no downtime.
Float Valve
OM-1000