Mounting Procedures

For proper operation of the electrode probe water level
control and the skimmer system, the humidifier must be
mounted level in both directions.
Access (460 mm minimum) for periodic removal of the
top cover is recommended. The cover is removed for
inspection and cleaning of the evaporating chamber. In
most cases, scale that forms on the heating elements
continuously flakes off as it forms and the loose scale
Figure 7-1: Mounting Support Methods
Floor Stand Method
560 mm
OM-646
Figure 7-2: Mounting Unit Below Duct
Mounting humidifier 460 mm below duct is recommended to facilitate cover removal.
OM-65

MOUNTING METHODS

Trapeze Hanger Method
Secure rods to
overhead construction
Provide 460 mm min.
clearance under duct
for cover removal
DRI-STEEM support
legs (optional)
Two-piece Escutcheon Plate
fastens to bottom of duct
(duct omitted for clarity)
Cover of VAPORSTREAM
Humidifier
settles to the bottom. A clean-out tray on the floor of
the evaporator may be removed periodically through
the front clean-out opening. Allow space for withdrawal
of the tray when installing the humidifier.
In some installations, an overflow drain pan may be
necessary to prevent possible damage to flooring. This
may be caused by a rapid or sudden drainage of the
contents of the humidifier. The drain pan must be
connected to the sanitary waste water system.
Steam Dispersion
Tube
Threaded rod of
size required
Angle or channel
of size required
Cleanout
OM-647
3 Heater
6 Heater
9 Heater
12 Heater
Clamp
Cut hole in duct large
enough to allow
passage of hose clamp
460 mm min.
Wall Brackets Method
625 mm
DRI-STEEM
wall brackets
(optional)
2 required
OM-648
Dimensions
Unit
A
480 mm
480 mm
760 mm
915 mm
Steam Dispersion
Tube
Vapor Hose
Bottom of Duct
Two-piece Escutcheon Plate
Cover of VAPORSTREAM
Humidifier
OM-66
A
7