State-of-the-art technology in a
simple, low-maintenance humidifier.
This humidifier is designed to be
used with either softened or
unsoftened water (preferably soft-
ened). The probe-type level control
system requires water conductivity
of 100 micromhos/cm (2 grains/gal)
minimum to function, and therefore
will not operate on water treated by
reverse osmosis or deionization.
However, VAPORSTREAM
VLC humidifiers are available for use
with these water types. The stan-
dard humidifier can be converted in
the field to a VLDI model. See
below.
VAPORSTREAM VLDI
Option
For use with deionized or reverse
osmosis water. This unit produces
chemical-free steam and reliable,
accurate humidification control. It is
virtually maintenance-free with no
wasted water, no wasted heat, and
very little or no downtime.
®
Model
3