VAPORSTREAM VLC Installation Instructions And Maintenance Operations Manual page 14

Electric steam humidifiers
Table of Contents

Advertisement

Figure 14-1: Shielded Cable Drain Wire Connection to Earth Bar
To Control Board
Shield Ground
For maximum E.M.C. effectiveness, all humidity, temperature and air flow controls should be wired using multi-
conductor shielded plenum-rated cable with a drain wire for the shield. The drain wire should be connected to the
shield ground terminal with its length kept to less than 50 mm.
Table 14-1: Conduit and Wire Size
Incoming Wire Size
**Amp Draw
AWG
0-12.5
14
12.6-16.7
12
16.8-25.0
10
25.1-41.7
8
41.8-54.2
6
54.3-70.8
4
70.9-95.8
2
95.9-108.3
1
108.4-145.8
2/0
Table 14-2: Conduit and Wire Size
Incoming Wire Size
**Amp Draw
AWG
0-10.0
14
10.1-13.3
12
13.4-20.0
10
20.1-33.3
8
33.4-43.3
6
43.4-56.7
4
56.8-76.7
2
76.8-86.7
1
86.8-116.7
2/0
* For use with star wiring for 240V heaters used with 415V power supply.
** Refer to Amp Draw on Rating Plate.
14
INSTALLATION REQUIREMENTS
Sensor Wires
Drain Wire (less than 50 mm)
Conduit Size (Ø mm)
2 Conductor
and Ground
KcMIL (mm2)
2.5
20
4.0
25
6.0
25
10.0
32
16.0
32
25.0
40
35.0
50
50.0
50
70.0
63
Conduit Size (Ø mm)
4 Conductor and
Ground*
KcMIL (mm2)
2.5
32
4.0
32
6.0
32
10.0
40
16.00
40
25.0
50
35.0
63
50.0
63
70.0
3 Conductor
Table 14-3: Fuse/Breaker
and Ground
Requirements
25
**Amp Draw
32
32
8.8-13.0
32
13.1-17.4
40
17.5-19.2
50
19.3-21.7
50
21.8-26.1
63
26.2-29.1
63
29.2-30.4
30.5-34.7
34.8-39.1
39.2-43.5
43.6-52.2
52.3-60.9
61.0-69.6
69.7-78.3
78.4-87.0
87.1-95.7
95.8-104.4
104.5-113.1
113.2-121.8
121.9-130.5
To Sensor
Fuse Size (A)
0-8.7
10
15
20
25
25
30
35
35
40
45
50
60
70
80
90
100
110
120
130
140
150