Operation - Samlexpower SEC-1260A Owner's Manual

Switch mode, automatic, lead acid battery charger 3 stage (iuou)
Table of Contents

Advertisement

SWITCHING ON / OFF
The charger is s
witched on /off with the illuminated AC input power on / off switch (9) located
on the rear panel of the unit. The switch is illuminated Red when switched on.
INDICATION OF NORMAL OPERATION AND CHARGING STATUS
When the charger is switched on without any load, the Charging Indicator LED (4) on the
front panel turns Red, Orange and then Green. The fan (11) will come on momentarily and
switch off. If a Remote Panel is connected, its Green LED "Power" will light and the other 3
LEDs will light in sequence - "I" Phase (Red), "Uo" Phase (Yellow) and then "U" Phase (Green).
If a battery or load is connected, the color of the Charging Indicator (4) on the front panel will
indicate the charging status as follows:
Charging Indicator LED (4) on the front panel is Red – Indicates that charger is in
Stage 1 - Constant Current, Bulk Charge Mode ("I" Phase) and is delivering current as follows:
SEC-1260A:
60 A to 48 A when in Normal Mode
30 A +/- 1A to 24 A when in Half Power Mode
SEC-1280A:
80 A to 64 A when in Normal Mode
40 A +/- 1A to 32 A when in Half Power Mode
SEC-2440A:
40 A to 32 A when in Normal Mode
20 A +/- 1A to 16 A when in Half Power Mode
Charging Indicator LED (4) on the front panel is Orange – Indicates that the charger
is in Stage 2 – Constant Overcharge Voltage, Timed Absorption / Boost Charge Stage ( "Uo"
Phase) and is delivering the following current:
SEC-1260A
> than 8.5A +/- 1A and < 48 A (when moving from Float Phase "U" to
(Normal Mode)
Boost Phase "Uo") or
< 48 A and > 6 A +/- 0.5A (When moving from Boost Phase "Uo"
to Float Phase "U")
SEC-1260A
> than 4.25A +/- 1A and < 24 A (when moving from Float Phase "U"
(Half Power Mode) to Boost Phase "Uo") or
< 24 A and > 3 A +/- 0.5A (When moving from Boost Phase "Uo"
to Float Phase "U")
SEC-1280A
> than 10A +/- 1A and < 64 A (when moving from Float Phase "U" to
(Normal Mode)
Boost Phase "Uo") or
< 64 A and > 8 A +/- 0.5A (When moving from Boost Phase "Uo"
to Float Phase "U")
SEC-1280A
> than 5A +/- 1A and < 32 A (when moving from Float Phase "U"
(Half Power Mode) to Boost Phase "Uo") or
< 32 A and > 4 A +/- 0.5A (When moving from Boost Phase "Uo"
to Float Phase "U")
SEC-2440A
> than 5A +/- 1A and < 32 A (when moving from Float Phase "U" to
(Normal Mode)
Boost Phase "Uo") or
< 32 A and > 4 A +/- 0.5A (When moving from Boost Phase "Uo"
to Float Phase "U")
SEC-1240A
> than 2.5A +/- 1A and < 16 A (when moving from Float Phase "U"
(Half Power Mode) to Boost Phase "Uo") or
< 16 A and > 2 A +/- 0.5A (When moving from Boost Phase "Uo"
to Float Phase "U")
Charging Indicator LED (4) on the front panel is Green – Indicates that the charger is in Stage 3 - Constant
Voltage, Float or Maintenance Charge Mode ("U" Phase). The charger is delivering
1260A), < 10 A +/- 0.5 A (SEC-1280A) or < 2.5 A +/- 0.5 A (SEC- 2440A).
battery is fully charged, it will draw very low current to compensate for its self discharge.

OPERATION

The battery is fully charged. When the
Page 22
< 8.5 A +/- 0.5 A (SEC-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sec-1280aSec-2440a

Table of Contents