WIRING DIAGRAM

PKA-RP35HAL
[Explanation of symbols]
Symbol
I.B
Indoor controller board
CN2L
Connector (LOSSNAY)
CN32
Connector ( Remote switch)
CN41
Connector (HA terminal-A)
CN51
Connector (Centrally control)
CN90
Connector (Remote operation adapter)
DSA
Surge absorber
FUSE
FUSE(T3.15AL250V)
LED1
Power supply (I.B)
LED2
Power supply (R.B)
LED3
Transmission (Indoor-outdoor)
SW1
Switch (Model selection) See table 1
SW2
Switch (Capacity code) See table 2
SWE
Connector (Emergency operation)
X1
Relay (Drain pump (option))
ZNR01,02 Varistor
Drain pump (option) power supply
CNP
(Drain pump (option))
CN4F
Drain float switch (Drain pump (option))
R.B
Wired remote controller(option)
TB6
Terminal block (Remote controller transmission line)
I.B
SWE
ON
OFF
1
Refer to
1
tables
CN2L
1and 2
(RED)
CN151
CN20
(WHT)
(RED)
1
5
M
t
Notes:
1. SymboIs used in wiring diagram above are,
2. Indoor and outdoor connecting wires have poIarities, make sure to match terminal
numbers (S1, S2, S3) for correct wirings.
3. Since the outdoor side electric wiring may change, be sure to check the outdoor unit
electric wiring diagram for servicing.
4. This diagram shows the wiring of indoor and outdoor connecting wires. (specification of
230V), adopting superimposed system for power and signal.
1: When work to supply power separately for indoor and outdoor units apply, refer to Fig 1.
2: For power supply system of this unit, refer to the caution label located near this diagram.
PKA-RP50HAL
Name
MS
3~
1
CNMF
(WHT)
T11
DB1
ZNR01
U
ZNR02
LED1
U
LED3
X1
LED2
CNP(BLU)
9
1
3
CN90
CN32
(WHT)
(WHT)
2
1
4
1
5
CN41
CN51
(WHT)
(WHT)
CN44
CN4F
(WHT)
(WHT)
1
2
1
4
1
4
When attaching
drain pump(option),
remove the jumper
t
t
TH1
TH2 TH5
connector CN4F
and fit the drain
float switch (FS).
: Connector,
Symbol
Name
M
Vane motor
MS
Fan motor
S.W
Switch board
SWE2
Emergency operation
TB2
Terminal block(Indoor unit Power (option))
TB4
Terminal block (Indoor/outdoor connecting line)
TB5
Terminal block (Remote controller transmission line(option))
TH1
Room temp. Thermistor
(0 /15ΚΩ, 25 /5.4ΚΩ Detect)
TH2
Pipe temp. Thermistor/liquid
(0 /15ΚΩ, 25 /5.4ΚΩ Detect)
TH5
Cond./eva. temp. Thermistor
(0 /15ΚΩ, 25 /5.4ΚΩ Detect)
W.B
Pcb for wireless remote controller
LED1
LED (Operation indication : Green)
LED2
LED (Preparation for heating: Orange)
REC1
Receiving unit
DCL
REACTOR
DP
DRAIN PUMP (OPTION)
FS
DRAIN FLOAT SWITCH (OPTION)
DCL
6
FUSE
1
YLW
YLW
YLW
S1
3
ORN
ORN
S2
5
S3
BLK
CN01
(BLK)
DSA
DP
3
M
1
1~
S.W
ORN
3
2
CN3C
BRN
(BLU)
1
LDSWE(B)
LDSWE(A)
W.B
(BLU)
6
CNRU
RU
(WHT)
LD101(B) REC1
LED1
LED2
CN22
1
(BLU)
2
When attaching drain
pump (option)
1
4
FLOAT SW
CN4F
(WHT)
FS
: Terminal (block).
9
<Table 1>
SW1
(MODEL SELECTION)
SETTING
TB4
1 2 3 4 5
TO
ON
OUTDOOR
OFF
UNIT
<Table 2>
SW2 (CAPACITY CODE)
MODELS
SETTING
1 2 3 4 5
RP35
1 2 3 4 5
SWE2
RP50
R.B
BLU
1
1
BLU
2
2
TB5
TB6
(OPTION PARTS)
1(Fig. 1)
CN01
I.B
(BLK)
TB2
YLW
RED
1
L
POWER SUPPLY
ORN
BLU
3
~(1PHASE)
N
GRN/YLW
5
230V 50Hz
TB4
YLW
ORN
S1
ORN
S2
BRN
I.B
S3
INDOOR/OUTDOOR
1
3
COMMUNICATION
CN3C(BLU)
ON
OFF
ON
OFF
TO OUTDOOR
UNIT