Duct Collar Installation Instructions - Accurex 470400 Installation, Operation And Maintenance Manual

Accurex model proximity (backshelf) kitchen hood
Table of Contents

Advertisement

Duct Collar Installation
Exhaust Ducts
1. If the exhaust duct has been factory mounted, skip this section.
. The exhaust duct must be located within the shaded region of Fig. 0. Note dimensions.
Dimension Y assumes a 3 in. (76. mm) integral airspace on the hood back. When no 3 in.
(76. mm) integral airspace is present, Y=0 in. (0 mm).
3. Cut out appropriate size hole to match the duct collar provided.
4. The exhaust duct connection is to be a continuous liquid-tight weld.
x
X= 1 in. (304.8 mm)
Y= 3 in. (76. mm)
Supply Ducts
Proximity hoods do not have integral supply plenums. Reference External Supply Plenums (Page 7).
Fire System Installation
The final fire system hook-up must be completed at this time. Unobstructed access is required for the
fire system installer to make plumbing connections to various locations on the hood top. Do not install
any enclosures until the fire system installation is complete.
14
y
EXHAUST PLENUM
DUCT CUT OUT AREA
FRONT OF HOOD
HANGER BRACKET
Fig. 0