Accurex 470400 Installation, Operation And Maintenance Manual page 18

Accurex model proximity (backshelf) kitchen hood
Table of Contents

Advertisement

B. Supply (If Applicable):
Example for Perforated Face Supply
1. Hood set up
If the make-up air unit has a temperature control, it should be used to keep the supply air at the
desired room discharge air temperature.
. Measure Velocities
Divide the perforated face panel into a grid of equal areas, each approximately 4 in. (100 mm)
square.
Measure the velocity at the center of each grid area. A digital .75 in. (70 mm) rotating vane
anemometer or equivalent is suggested. The center of the anemometer should be held tight to
the face of the panel, and parallel to the filter. Both squareness and distance are important for
accuracy. Calculate the average velocity of the panel.
3. Measure the length, height, and width of the perforated face panel.
4. Calculate the perforated face panel volume in CFM by using the following formula:
Volume
=
Volume
=
5. Calculate the system's volume by repeating the process for the remaining panels and adding
the individual panel volumes together.
Filter Readings (fpm)
260
250
270
275
290
285
285
275
Example: Face Supply Hood with three 28 in. (.711 m) Perforated Panels
Measured velocities in FPM for one perforated panel
Average Velocity
(Imperial)
(Metric)
Measure Length and Height = 8 in. (.711 m) long perforated panels x 16 in. (.406 m) high
Volume for one panel =
Total system volume
18
Avg. Velocity
Length (in.) * Height (in.) * 0.005
*
Avg. Velocity
Length (m) * Height (m) * 0.7
*
255
260
250
255
265
270
280
265
265
270
280
280
275
290
295
280
260
270
265
260
Sum of Velocity Readings
=
Number of Readings
60 + 50 + ... + 65 + 60
=
8
4755 + 457 + ... + 4846 + 4755
=
8
Conversion
Average
x
Factor
Velocity
=
0.005
x
70.7 fpm
=
0.7
x
4951 m/hr
= (Panel 1 Volume) + (Panel  Volume) + (Panel 3 Volume)
=
606.4
+
=
109
+
Filter Readings (m/hr)
4755 4572 4663 4755 4572 4663 4846
4938 5029 4938 5121 4846 4846 4938
5304 5212 5121 5121 5029 5304 5395
5212 5029 5121 4755 4938 4846 4755
= 70.7 fpm
= 4951 m/hr
x Length x
Height
x
8
x
x
.711
x
.406
614.3
+
593.8
1044
+
1009
16
=
606.4 cfm
=
109 m
3
/hr
=
1814.5 cfm
=
308 m
3
/hr