Accurex 470400 Installation, Operation And Maintenance Manual page 10

Accurex model proximity (backshelf) kitchen hood
Table of Contents

Advertisement

Full Enclosure Panels
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork
attached and fire system connections completed.
1. Tack-weld or clamp end enclosure panels onto standing seam (clamps provided).
. Attach the end enclosure panels to the wall (fasteners by others).
3. Position the front enclosure panel(s) on the hood and bolt to the end enclosure panels with the
5/16 in. bolts provided.
4. Tack-weld or clamp the front enclosure panel(s) to the standing seam. If clamps are used, they
must be positioned 4 in. (100 mm) from the ends and in the center of the front enclosure panel.
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk.
(GE SCS1009, or its equivalent). The caulk is not provided.
6. Installation instructions may not be applicable for concrete ceilings.
Bolt Here
10
End Enclosures
Standing Seams
Front Enclosure(s)
Fig. 15