4.7 — Battery Maintenance
The battery should be regularly inspected per the Service Schedule:
1.
With the generator shut down, lift the lid and remove the front panel.
2.
Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
3.
Check the battery fluid level of unsealed batteries, and if necessary, fill with distilled water only. DO NOT use tap water. Also, have the
Dealer or a qualified Service Technician check the state of charge and condition.
Do not dispose of the battery by incineration. The battery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. Strictly observe the following precau-
tions when working on batteries:
Remove the 7.5 Amp fuse from the generator control panel.
Remove all jewelry—watches, rings, metal objects, etc.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metallic objects on top of the battery.
Disconnect the charging source prior to connecting or disconnecting battery terminals.