2.4.3 — Fuel Requirements
The engine has been fitted with a dual fuel carburetion system. The unit will run on natural gas or LP gas (vapor), but it has been factory set to
run on natural gas. The fuel system will be configured for the available fuel source during installation.
Recommended fuels should have a btu content of at least 1,000 Btus per cubic foot (37.26 megjoules per cubic meter) for natural gas, or at least
2,500 Btus per cubic foot (93.15 megajoules per cubic meter) for LP gas (vapor).
NOTE: If converting to LP gas from natural gas, a minimum LP tank size of 250 gallons (946 liters) is recommended. See the Installa-
tion Manual for complete procedures and details.
Gaseous fuels such as natural gas and liquid propane gas are highly explosive. Even the
$
slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted.
Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air
and tends to settle in low areas
2.4.4 — Battery Requirements
Group 26R, 12V, minimum 525CCA (Generac Part No. 0H3421S).
For proper battery maintenance procedures, see Section 4 Maintenance.
2.4.5 — Battery Charger
The battery charger is integrated into the control panel module in all models. It operates as a "Smart Charger" which ensures output charging lev-
els are safe and continuously optimized to promote maximum battery life.
2.4.6 — Engine Oil Requirements
For proper oil viscosity, see chart in Figure 4-1: Recommended Oil Based on Temperature.
2.5 — Accessories
There are performance enhancing accessories available for air-cooled generators.
Accessory
Cold Weather Kit
Scheduled Maintenance Kit
Auxiliary Transfer Switch Lock-
out
Fascia Skirt Wrap
Mobile Link™
Touch-Up Paint Kit
Contact a Dealer for additional information on accessories.
Automatic Standby Generator Owner's Manual
Description
Recommended in areas where temperatures regularly fall below 32º F (0º C).
Includes all pieces necessary to perform maintenance on the generator along with oil recommendations.
Enables any of the transfer switches to completely lock out one large electrical load by tying into its control system.
Standard on all 20kW units. It is available for all other current production air-cooled units. It snaps together to pro-
vide a smoothing, contoured look as well as rodent/insect protection.
Provides a personalized web portal that displays the generator's status, maintenance schedule, event history and
much more. This portal is accessible via computer, tablet or smart phone. Sends emails and/or text notifications the
moment there is any change in the generator's status. Notification settings can be customized to what type of alert is
sent and how often. For more information, visit www.standbystatus.com.
Very important to maintain the look and integrity of the generator enclosure. This kit includes touch-up paint and