Drainage Piping Work; Electrical Work - Mitsubishi Electric PLA-RP Installation Manual

Table of Contents

Advertisement

6. Drainage piping work

Max. 20m
1.5–2m
A
B
K
B
D
E
D
F
F
H
I
Fig. 6-1
A
B
C
L
F
11
25
25
25
D E
E
Fig. 6-2

7. Electrical work

A
B
C
E
D
J,K
Fig. 7-1
Indoor unit model
Indoor unit power supply (Heater)
Indoor unit input capacity (Heater)
Main switch (Breaker)
Indoor unit power supply (Heater)
Indoor unit power supply (Heater) earth
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Indoor unit (Heater) L-N
Indoor unit-Outdoor unit S1-S2
Indoor unit-Outdoor unit S2-S3
Remote controller-Indoor unit
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. A 10 m wire is attached in the remote controller accessory.
*3. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are not electrically insulataed by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 57)
3. Install an earth longer and thicker than other cables.
6
C
Max. 15cm
J
F
L
M
D
F
G
(mm)
G
C,K
H
I
K
G
F
L
N
S1
S2
S3
1
2
H
I
*1
*2
*3
*3
*3
*3
6.1. Drainage piping work (Fig. 6-1)
• Use VP25 (O. D. ø32 PVC TUBE) for drain piping and provide 1/100 or more down-
ward slope.
• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.
1 Correct piping
2 Wrong piping
A Insulation (9 mm or more)
B Downward slope (1/100 or more)
Grouped piping
D O. D. ø32 PVC TUBE
E Make it as large as possible
F Indoor unit
G Make the piping size large for grouped pip-
ing.
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 6-2)
(Affix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).
(Affix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
A Unit
B Insulating material
C Band (large)
D Drain port (transparent)
E Insertion margin
F Matching
G Drain pipe (O.D. ø32 PVC TUBE)
J
H Insulating material (purchased locally)
I Transparent PVC pipe
J O.D. ø32 PVC TUBE (Slope 1/100 or more)
K Band (small)
L Drain socket
7.1. Indoor unit (Fig. 7-1)
1. Remove the two electrical wiring service panels.
2. Wire the power cable and control cable separately through the respective wiring
entries given in the diagram.
• Do not allow slackening of the terminal screws
• Leave excess cable so that the electrical box can be suspended below the unit
during servicing. (Approx. 50 to 100 mm)
A Entry for control cable
B Entry for power
C Clamp
D Service panel for indoor controller switch setting
E Service panel for electrical wiring
F Electric heater power supply terminals (PLH models)
G Indoor / Outdoor unit connecting terminals
H Remote controller connector
I Secure with the clamp
J Intake sensor
K Holder
PLA
3 × 2.5 (polar)
1 × Min. 2.5
2 × 0.69 (Non-polar)
AC 220-230-240V
DC24V
DC14V
C Support metal
K Air bleeder
L Raised
M Odor trap
H Downward slope (1/100 or more)
I O. D. ø38 PVC TUBE for grouped piping.
(9 mm or more insulation)
J Up to 85 cm
PLH
~/N (single), 50Hz, 220-230-240V
16 A
2 × Min. 1.5
1 × Min. 1.5
3 × 2.5 (polar)
1 × Min. 2.5
2 × 0.69 (Non-polar)
AC 220-230-240V
AC 220-230-240V
DC24V
DC14V

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pla-aaMr.slim pla-rpMr.slim pla-aa

Table of Contents