Goodman PC 13 SEER R-410A Technical Manual

Goodman PC 13 SEER R-410A Technical Manual

Package air conditioners with r-410a

Advertisement

Quick Links

TECHNICAL MANU
TECHNICAL MANU AL
TECHNICAL MANU
TECHNICAL MANU
TECHNICAL MANU
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury
due to improper service procedures or services performed by an unqualified person.
*PC 13 SEER R-410A
Package Air Conditioners
with R-410A
Refer to Service Manual RS6300011 (Horizontal) for installation, operation,
and troubleshooting information.
All safety information must be followed as provided in the Service Manual.
Refer to the appropriate Parts Catalog for part number information.
Models listed on page 3.
Copyright © 2008 - 2013 Goodman Manufacturing Company, L.P.
AL
AL
AL
AL
RT6322006r10
September 2013

Advertisement

loading

Summary of Contents for Goodman PC 13 SEER R-410A

  • Page 1 RT6322006r10 This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury September 2013 due to improper service procedures or services performed by an unqualified person.
  • Page 2: Product Identification

    Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death. Installation and repair of this unit Goodman will not be responsible WARNING WARNING WARNING...
  • Page 3 PRODUCT IDENTIFICATION The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. GPC1324H41AA GPC1330H41AA GPC1336H41AA GPC1342H41AA GPC1348H41BA GPC1360H41BA 5 mm model specific information begins on page 28.
  • Page 4: Product Design

    PRODUCT DESIGN GPC Package Cooling Units are designed for outdoor instal- Location and Clearances lations only in either residential or light commercial applica- NOTE: To ensure proper condensate drainage, unit must be tions. installed in a level position. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow.
  • Page 5 PRODUCT DESIGN In installations where the unit is installed above ground level Refer to Roof Curb Installation Instructions for proper curb and not serviceable from the ground (Example: Roof Top in- installation. Curbing must be installed in compliance with stallations), the installer must provide service platform for ser- the National Roofing Contractors Association Manual.
  • Page 6: Product Dimensions

    PRODUCT DIMENSIONS *PC13[24-60]H41** BACK (DUCT OPENINGS) Chassis Model *PC1324 Small *PC1330 *PC1336 *PC1342 Medium *PC1349 *PC1348 38 3/4 Large *PC1360 38 3/4 Dimensions in inches...
  • Page 7 *PC13[24-60]H41** ACCESSORIES ACCESSORIES - *PC/*PH****H UNITS Part Number Description OT18-60A Outdoor Thermostat Kit w/Lockout Stat OT/EHR18-60 Emergency Heat Relay Kit Electric Heat Kit PCCP101-103 Roof Curb PCP101-103 Downflow Plenum Kit PCP101-103R8 Downflow Plenum Kit w/ R-8 Insulation PCEC101-103 Downflow Economizer for GPC-(H) A/C - To Be Used With PCP101-103 PCEH101-103 Downflow Economizer for GPH-(H) Heat Pump - To Be Used With PCP101-103 PCMD101-103...
  • Page 8 PRODUCT DESIGN *PC13[24-60]H41** ELECTRICAL DATA (*Blower Only, Heat Mode) Circuit #1 Circuit #2 Maximum Maximum Actual Model and Minimum Circuit Minimum Circuit kW & BTU Overcurrent Overcurrent Heat Kit Usage Ampacity Ampacity at 240V Protection (amps) Protection (am ps) at 208 / 240V at 2 08 / 240V at 208 / 240V at 208 / 240V...
  • Page 9: Blower Performance Data

    *PC13[24-60]H41** BLOWER PERFORMANCE DATA Dry Coil Data E.S.P (In. of H M odel Spee d Volts 0 .1 0 .2 0 .3 0 .4 0 .7 0 .8 Lo w WA TTS WA TTS 1,185 1,130 1,070 1,010 H ig h WA TTS 1,150 1,080...
  • Page 10 BLOWER PERFORMANCE DATA...
  • Page 11 PACKAGE COOLING SPECIFICATIONS GPC13[24-42]H41AA GPC1324H41AA GPC1330H41AA GPC1336H41AA GPC1342H41AA COOLING COOLING CAPACITY, BTUH 24,000 28,600 36,000 41,000 CAPACITY SEER 13.0 13.0 13.0 13.0 VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 UNIT ELECTRICAL AMPS (TOTAL) 10.5 13.16 20.06 22.2 SPECIFICATION MINIMUM CIRCUIT AMPACITY 12.5 15.6 24.2...
  • Page 12 PACKAGE COOLING SPECIFICATIONS GPC13[48-60]H41BA GPC1348H41BA GPC1360H41BA COOLING COOLING CAPACITY, BTUH 45,500 57,500 SEER 13.0 13.0 CAPACITY UNIT VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 ELECTRICAL AMPS (TOTAL) 24.17 33.6 SPECIFICATION MINIMUM CIRCUIT AMPACITY 29.2 40.2 MAXIMUM OVERCURRENT PROTECTION COMPRESSOR TYPE SCROLL SCROLL RATED LOAD AMPS 19.9 26.4 LOCKED ROTOR AMPS...
  • Page 13 COOLING PERFORMANCE DATA GPC1324H41AA...
  • Page 14 COOLING PERFORMANCE DATA GPC1324H41AA...
  • Page 15 COOLING PERFORMANCE DATA GPC1330H41AA...
  • Page 16 COOLING PERFORMANCE DATA GPC1330H41AA...
  • Page 17 GPC1336H41AA COOLING PERFORMANCE DATA...
  • Page 18 COOLING PERFORMANCE DATA GPC1336H41AA...
  • Page 19 COOLING PERFORMANCE DATA GPC1342H41AA...
  • Page 20 COOLING PERFORMANCE DATA GPC1342H41AA...
  • Page 21 COOLING PERFORMANCE DATA GPC1348H41BA...
  • Page 22 COOLING PERFORMANCE DATA GPC1348H41BA...
  • Page 23 COOLING PERFORMANCE DATA GPC1360H41BA/CA...
  • Page 24 COOLING PERFORMANCE DATA GPC1360H41BA/CA...
  • Page 25: Cooling Performance Data

    COOLING PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
  • Page 26: Wiring Diagrams

    GPC13[24-42]H41AA WIRING DIAGRAMS GPC1348H41BA NOTE #4 EBTDR SEE NOTE #6 XFMR-R XFMR-C SPEED LVJB RCCF (IF USED) SEE NOTE 5 (TRANS240V) CONTROL (M1) RD (COM) HIGH 3 SPEED 2 SPEED OPTIONAL COMP NOTE #3 SUPPLY VOLTAGE 208-240/1/60 COMPONENT LEGEND FACTORY WIRING SEE NOTE #3 LINE VOLTAGE BLOWER INTERLOCK RELAY...
  • Page 27 WIRING DIAGRAMS GPC1360H41BA NOTE #3 SEE NOTE 5 LVJB RCCF (IF USED) SEE NOTE 4 CONTROL C L G N 1 2 3 COMP SEE NOTE 2 COMPONENT LEGEND FACTORY WIRING SUPPLY VOLTAGE LINE VOLTAGE CONTACTOR 208-240/1/60 LOW VOLTAGE CONDENSER MOTOR OPTINAL HIGH COMP COMPRESSOR...
  • Page 28: Product Design

    *PC 13 SEER R-410A 5 mm Package Air Conditioners GPC1324H41AB GPC1324H41B* *PC1324H41C* GPC1330H41AB GPC1330H41B* *PC1330H41C* GPC1336H41AB GPC1336H41B* *PC1336H41C* GPC1342H41AB GPC1342H41B* *PC1342H41C* GPC1349H41AA GPC1349H41B* *PC1349H41C* GPC1360H41BB *PC1360H41C* *PC1360H41D* PRODUCT DESIGN capacitor type motors with the exception of the *PC1360H41** *PC Package Cooling Units are designed for outdoor instal-...
  • Page 29 PRODUCT DESIGN Location and Clearances In installations where the unit is installed above ground level NOTE: To ensure proper condensate drainage, unit must be and not serviceable from the ground (Example: Roof Top installed in a level position. installations), the installer must provide service platform for service person with rails or guards in accordance with local codes or ordinances or in their absence with the latest edi- tion of the Uniform Mechanical Code Section 305.
  • Page 30 PACKAGE COOLING SPECIFICATIONS GPC13[24-36]H41AB GPC1324H41AB GPC1330H41AB GPC1336H41AB COOLING COOLING CAPACITY, BTUH 24,000 28,600 36,000 CAPACITY SEER 13.0 13.0 13.0 UNIT VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 ELECTRICAL AMPS (TOTAL) 16.1 15.76 20.06 SPECIFICATION MINIMUM CIRCUIT AMPACITY 19.5 24.2 MAXIMUM OVERCURRENT PROTECTION COMPRESSOR TYPE SCROLL...
  • Page 31 GPC1342H41AB GPC1349H41AA PACKAGE COOLING SPECIFICATIONS GPC1360H41BB GPC1342H41AB GPC1349H41AA GPC1360H41BB COOLING COOLING CAPACITY, BTUH 41,000 45,500 57,500 CAPACITY SEER 13.0 13.0 13.0 VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 UNIT AMPS (TOTAL) 22.17 24.17 33.6 ELECTRICAL MINIMUM CIRCUIT AMPACITY 26.6 29.2 40.2 SPECIFICATION MAXIMUM OVERCURRENT PROTECTION COMPRESSOR TYPE...
  • Page 32 PACKAGE COOLING SPECIFICATIONS *PC13[24-30]H41B*/C* GPC1324H41B* GPC1324H41C* APC1324H41C* *PC1330H41B*/C* COOLING CAPACITY, BTUH 24,000 24,000 22,800 28,600 COOLING CAPACITY SEER 13.0 13.0 13.0 13.0 VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 AMPS (TOTAL) 10.5 10.3 16.1 15.76 UNIT ELECTRICAL SPECIFICATION MINIMUM CIRCUIT AMPACITY 12.5 12.2 19.5...
  • Page 33 *PC13[36-60]H41B*/C* PACKAGE COOLING SPECIFICATIONS *PC1336H41B*/C* *PC1342H41B*/C* *PC1349H41B*/C* *PC1360H41C*/D* COOLING CAPACITY, BTUH 36,000 41,000 45,500 57,500 COOLING SEER 13.0 13.0 13.0 13.0 CAPACITY UNIT VOLTAGE (NAMEPLATE) 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 AMPS (TOTAL) 20.06 22.17 24.17 33.6 ELECTRICAL MINIMUM CIRCUIT AMPACITY 24.2 26.6 29.2 40.2...
  • Page 34 COOLING PERFORMANCE DATA *PC1324H41AB/B*/C*...
  • Page 35 COOLING PERFORMANCE DATA *PC1324H41AB/B*/C*...
  • Page 36 COOLING PERFORMANCE DATA *PC1330H41AB/B*/C*...
  • Page 37 *PC1330H41AB/B*/C* COOLING PERFORMANCE DATA...
  • Page 38 COOLING PERFORMANCE DATA *PC1336H41AB/B*/C*...
  • Page 39 *PC1336H41AB/B*/C* COOLING PERFORMANCE DATA...
  • Page 40 *PC1342H41AB/B*/C* COOLING PERFORMANCE DATA...
  • Page 41 COOLING PERFORMANCE DATA *PC1342H41AB/B*/C*...
  • Page 42 *PC1349H41AA/B*/C* COOLING PERFORMANCE DATA...
  • Page 43 *PC1349H41AA/B*/C* COOLING PERFORMANCE DATA...
  • Page 44 COOLING PERFORMANCE DATA *PC1360H41BB/C*/D*...
  • Page 45 COOLING PERFORMANCE DATA *PC1360H41BB/C*/D*...
  • Page 46 COOLING PERFORMANCE DATA PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1.
  • Page 47: Wiring Diagrams

    *PC13[24-42]H41AB/B*/C* WIRING DIAGRAMS *PC1349H41AA/B*/C* NOTE #4 G EBTDR SEE NOTE #6 XFMR-R XFMR-C SPEED LVJB RCCF (IF USED) SEE NOTE 5 (TRANS240V) (M1) RD CONTROL (COM) HIGH 3 SPEED 2 SPEED OPTIONAL COMP NOTE #3 SUPPLY VOLTAGE 208-240/1/60 COMPONENT LEGEND FACTORY WIRING SEE NOTE #3 LINE VOLTAGE...
  • Page 48 WIRING DIAGRAMS *PC1360H41BB/C*/D* NOTE #3 SEE NOTE 5 LVJB RCCF (IF USED) SEE NOTE 4 CONTROL COMP SEE NOTE 2 COMPONENT LEGEND FACTORY WIRING SUPPLY VOLTAGE LINE V OLTAGE CONTACTOR 208-240/1/60 LOW VOLTAGE CONDENSER MOTOR OPTIONAL HIGH COMP COMPRE SSOR VOLTAGE EVAPORATOR MOTOR EQUIPMENT GROUND...