System Piping; Freeze Protection; Special Applications - PEERLESS Pinnacle PI-399 Installation And Operation Manual

Stainless steel gas boilers
Table of Contents

Advertisement

WATER PIPING AND CONTROLS
D. SYSTEM PIPING
1. Figure 3.3 shows a single boiler with one heating
zone and a Peerless Partner indirect water heater.
2. Figure 3.4 shows a single boiler with an additional
zone in which baseboard radiation is the heat load.
3. Figure 3.5 shows diverter tees used in combination
with conventional hydronic radiators on an
additional zone. A second boiler is also added to the
system. Notice that the boilers are piped in parallel
on the secondary loop. It is important that the
common headers are sized to match the system
piping. Smaller headers may result in flow
fluctuations through the boilers.
4. Figure 3.6 shows a system in which several different
types of loads and multiple boilers are shown. This
system illustrates how different temperature zones
can be supplied from the same source by mixing
down the temperature using a three way mixing
valve. Radiant flooring typically requires much lower
temperatures than baseboard radiation and indirect
water heating. Notice that a third boiler is included in
this system.
5. Figure 3.7 shows zone valves used in place of zone
circulators. Notice that this system utilizes reverse
return piping which makes it easier to balance the
system. If the heating zones are very different in
length, the balancing valves on the return side of
each loop are required.
E. FREEZE PROTECTION
1. Glycol for hydronic applications is specially
formulated for this purpose. It includes inhibitors
which prevent the glycol from attacking metallic
system components. Make certain that the system
fluid is checked for the correct glycol concentration
and inhibitor level.
2. Use only inhibited propylene glycol solutions of up
to 50% by volume. Ethylene glycol is toxic and can
chemically attack gaskets and seals used in hydronic
systems.
3. The antifreeze solution should be tested at least once
per year and as recommended by the antifreeze
manufacturer.
4. Antifreeze solutions expand more than water. For
example, a 50% by volume solution expands 4.8%
for a 148°F temperature rise while water expands
about 3% for the same temperature increase.
Allowance for this expansion must be considered in
sizing expansion tanks and related components.
5. The flow rate in systems utilizing glycol solution
should be increased compared with a water system
to compensate for increased heating capacity.
8
6. Due to increased flow rate and fluid viscosity the
circulator head requirement will increase. Contact the
pump manufacturer to correctly size the circulator for
a particular application based on the glycol
concentration and heating requirements.
7. A strainer, sediment trap, or some other means for
cleaning the piping system must be provided. It
should be located in the return line upstream of the
boiler and must be cleaned frequently during the
initial operation of the system. Glycol solution is
likely to remove mill scale from new pipe in new
installations.
8. Glycol solution is expensive and leaks should be
avoided. Weld or solder joints should be used where
possible and threaded joints should be avoided.
Make up water should not be added to the system
automatically when a glycol solution is used. Adding
make-up water may significantly dilute the system.
9. Check local regulations to see if systems containing
glycol solutions must include a back-flow preventer
or require that the glycol system be isolated from the
water supply.
10. Do not use galvanized pipe in glycol systems.
11. Use water that is low in mineral content and make
sure there are no petroleum products in the solution.
12. Mix solution at room temperature.
13. Do not use a chromate treatment.
14. Do not use glycol solution in a system that may
reach temperatures above 250°F.
15. Refer to Technical Topics, #2a published by the
Hydronics Institute Division of GAMA for further
glycol system considerations.
F.

SPECIAL APPLICATIONS

1. If the boiler is used in conjunction with a chilled
medium system, pipe the chiller in a separate
secondary loop.
a. Assure that the boiler circulator is disabled during
chiller operation so chilled water does not enter
the boiler.
b. Install a flow control valve (spring check valve) to
prevent gravity flow through the boiler.
c. See Figure 3.8 for recommended system piping.
2. For boilers connected to heating coils in a forced air
system where they may be exposed to chilled air
circulation, install flow control valves or other
automatic means to prevent gravity circulation of the
boiler water during cooling cycles. See Figure 3.9 for
illustration.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents