Tripp Lite PDUMH15AT Owner's Manual

Tripp Lite PDUMH15AT Owner's Manual

Switched/metered rack pdu with automatic transfer switch
Hide thumbs Also See for PDUMH15AT:

Advertisement

Quick Links

PDUMH15AT,PDUMH15ATNET
PDUMH20AT,PDUMH20ATNET
Español
Français
Copyright © 2009 Tripp Lite. All rights reserved. SmartOnline
200905008 93-2857.indb 1
Owner's Manual
Switched/Metered Rack PDU with

Automatic Transfer Switch

1111 W. 35th Street • Chicago, IL 60609 USA
(773) 869-1234 • www.tripplite.com
is a trademark of Tripp Lite.
2
3
3
3
5
5
5
7
8
10
10
10
10
11
11
12
12
13
25
5/5/2009 9:36:39 AM

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PDUMH15AT and is the answer not in the manual?

Questions and answers

Summary of Contents for Tripp Lite PDUMH15AT

  • Page 1: Table Of Contents

    6. Warranty and Warranty Registration Español Français 1111 W. 35th Street • Chicago, IL 60609 USA (773) 869-1234 • www.tripplite.com Copyright © 2009 Tripp Lite. All rights reserved. SmartOnline ™ is a trademark of Tripp Lite. 200905008 93-2857.indb 1 5/5/2009 9:36:39 AM...
  • Page 2: Important Safety Instructions

    1. Important Safety Instructions SAVE THESE INSTRUCTIONS This manual contains instructions and warnings that should be followed during the installation, operation, and storage of this product. Failure to heed these instructions and warnings will void the product warranty. • The PDU provides convenient multiple outlets, but it DOES NOT provide surge or line noise protection for connected equipment.
  • Page 3: Installation

    Secondary. The Primary input cord is permanently attached to the rear of the PDU. The Secondary input cord is detachable and connects to the IEC power inlet at the rear of the PDU (PDUMH15AT,PDUMH15ATNET - PDUMH15AT PDUMH20AT IEC-320-C14 inlet; PDUMH20AT, PDUMH15ATNET PDUMH20ATNET PDUMH20ATNET - IEC-320-C20 inlet).
  • Page 4: Networking The Pdu

    ™ UPS System. The UPS system must not share a circuit with a heavy electrical load (such as an air conditioner or PDUMH15AT, refrigerator). Under normal operating conditions, PDUMH15ATNET the PDU will distribute AC power from the Primary input source. Connect the Secondary...
  • Page 5: Dynamic Ip Address Assignment

    2. Installation ( continued ) 2.3.1 Dynamic IP Address Assignment Connect PDU to Network: While the PDU is powered, connect a standard Ethernet patch cable to the RJ-45 Ethernet port on the PDU. Note: This port is not compatible with PoE (Power over Ethernet) applications.
  • Page 6 Gateway address IP address [192.168.1.1]? 192.168.0.1 Gateway address IP address is 192.168.0.1 You can also change the root password, real-time clock and other settings. (Tripp Lite recommends against changing the default settings unless you are an advanced user with a specific purpose.) After you have finished entering settings, the PDU will save changes to memory and reboot (this may take several minutes).
  • Page 7: Testing Network Connection

    2. Installation ( continued ) 2.3 Networking the PDU ( continued ) 2.3.3 Testing Network Connection Access PDU with Web Browser: After an IP address has been assigned to the PDU, attempt to access it with a Web browser that supports ™...
  • Page 8: Features

    3. Features Primary AC Input Power Cord (Model PDUMH15AT/15ATNET):The cord is permanently attached to the PDU and has a NEMA 5-15P plug. Primary AC Input Power Cord (Model PDUMH20AT/20ATNET): The cord is permanently attached to the PDU and has a NEMA L5-20P plug.
  • Page 9 Do not connect anything to the port. For Models with SNMP Network Card Installed: PS/2 Port: Use this port to connect a Tripp Lite ENVIROSENSE environmental sensor to provide remote temperature/humidity monitoring and a dry contact interface to control and monitor alarm, security and telecom devices.
  • Page 10: Configuration And Operation

    4. Configuration and Operation 4.1 Automatic Transfer Switch When the Primary and Secondary inputs are both connected to Tripp Lite UPS Systems, the PDU operates as an Automatic Transfer Switch, providing redundant input power for high availability applications. Under normal operating conditions, the PDU will distribute power from the Primary input source, switching to the Secondary input source under certain conditions.
  • Page 11: Quick Test

    4. Configuration and Operation ( continued ) 4.1 Automatic Transfer Switch ( continued ) 4.1.3 Quick Test After installing the PDU and connecting equipment, you may test the Automatic Transfer Switch function by temporarily shutting down the UPS system connected to the Primary AC input. When the Primary input UPS is no longer supplying AC power, the PDU will switch from the Primary input to the Secondary input, and the...
  • Page 12: Technical Support

    Service under this Warranty can only be obtained by your delivering or shipping the product (with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609 USA. Seller will pay return shipping charges.

This manual is also suitable for:

Pdumh20atPdumh15atnetPdumh20atnet

Table of Contents