VIESMANN VITOCAL 300/350 Heat pump Brine/Water – 6.4 to 32.6 kW Water/Water – 8.4 to 43.0 kW Datasheet Part numbers and prices: see pricelist VITOCAL 300 Type BW and WW Up to 55 °C flow temperature Heat pump with electric drive for DHW and central heating in mono or dual-mode heating systems &...
Product description Type BW/BWH – heat from the ground: The Vitocal 300/350 extracts heat from the ground with the help of ground collectors or ground probes. The ground provides almost completely stable temperatures all the year round, enabling the Vitocal 300/350 to operate virtually independently of the outside temperature.
Page 3
& Achieves high performance factors: underfloor heating – up to 4.61 to DIN EN 255 with the Vitocal 300 BW & Vitocal 350 with 65 °C flow temperature for use in systems with (brine: 0 °C, flow temperature: 35 °C) radiators used in modernisation projects –...
Page 8
Operating point: B2 = brine inlet temperature 2 °C/W35 = heating water outlet temperature 55 °C. Operating point: B2 = brine inlet temperature 2 °C/W35 = heating water outlet temperature 65 °C. For further operating points, see the output diagrams. Always safeguard the min. throughput. With starting current limiter. VIESMANN VITOCAL 300/350...
Page 9
Operating point: W8 = groundwater inlet temperature 8 °C/W55 = heating water outlet temperature 55 °C. Operating point: W8 = groundwater inlet temperature 8 °C/W65 = heating water outlet temperature 65 °C. For further operating points, see the output diagrams. Always safeguard the min. throughput. With starting current limiter. VIESMANN VITOCAL 300/350...
Page 10
Specification (cont.) Dimensions Left illustration - Vitocal 300/350, single stage; right illustration: Vitocal 300, two-stage A Primary OUT (brine) HR Heating return B Primary IN (brine) HV Heating flow C Cable entries VIESMANN VITOCAL 300/350...
Page 12
Output diagrams for the Vitocal 300 (single stage) Vitocal 300, type BW 106 and WW 106 (single stage) Note COP details in the following tables and diagrams calculated with reference to DIN EN 255. Performance data type BW 106 Operating point...
Page 13
Output diagrams for the Vitocal 300 (single stage) (cont.) Vitocal 300, type BW 108 and WW 108 (single stage) Performance data type BW 108 Operating point B0/W35 B2/W45 B2/W55 Heating output 8.30 8.50 8.10 Refrigerating capa- 6.50 6.25 5.30 city Power consumption 1.80...
Page 14
Output diagrams for the Vitocal 300 (single stage) (cont.) Vitocal 300, type BW 110 and WW 110 (single stage) Performance data type BW 110 Operating point B0/W35 B2/W45 B2/W55 Heating output 10.80 11.10 10.60 Refrigerating capa- 8.40 8.10 7.00 city Power consumption 2.40...
Page 15
Output diagrams for the Vitocal 300 (single stage) (cont.) Vitocal 300, type BW 113 and WW 113 (single stage) Performance data type BW 113 Operating point B0/W35 B2/W45 B2/W55 Heating output 14.00 14.40 13.90 Refrigerating capa- 10.95 10.65 9.35 city Power consumption 3.05...
Page 16
Output diagrams for the Vitocal 300 (single stage) (cont.) Vitocal 300, type BW 116 and WW 116 (single stage) Performance data type BW 116 Operating point B0/W35 B2/W45 B2/W55 Heating output 16.30 16.70 16.10 Refrigerating capa- 12.70 12.20 10.70 city Power consumption 3.60...
Page 17
Output diagrams for the Vitocal 300 (two-stage) Vitocal 300, type BW 212 and WW 212 (two-stage) Note COP details in the following tables and diagrams calculated with reference to DIN EN 255. Performance data type BW 212 Operating point B0/W35...
Page 18
Output diagrams for the Vitocal 300 (two-stage) (cont.) Vitocal 300, type BW 216 and WW 216 (two-stage) Performance data type BW 216 Operating point B0/W35 B2/W45 B2/W55 Heating output 16.60 17.00 16.20 Refrigerating capa- 13.00 12.50 10.60 city Power consumption 3.60...
Page 19
Output diagrams for the Vitocal 300 (two-stage) (cont.) Vitocal 300, type BW 220 and WW 220 (two-stage) Performance data type BW 220 Operating point B0/W35 B2/W45 B2/W55 Heating output 21.60 22.20 21.20 Refrigerating capa- 16.80 16.20 14.00 city Power consumption 4.80...
Page 20
Output diagrams for the Vitocal 300 (two-stage) (cont.) Vitocal 300, type BW 226 and WW 226 (two-stage) Performance data type BW 226 Operating point B0/W35 B2/W45 B2/W55 Heating output 28.00 28.80 27.80 Refrigerating capa- 21.90 21.30 18.70 city Power consumption 6.10...
Page 21
Output diagrams for the Vitocal 300 (two-stage) (cont.) Vitocal 300, type BW 232 and WW 232 (two-stage) Performance data type BW 232 Operating point B0/W35 B2/W45 B2/W55 Heating output 32.60 33.40 32.20 Refrigerating capa- 25.40 24.40 21.40 city Power consumption 7.20...
Page 22
10.30 9.45 city Power consumption 2.70 4.30 5.15 Coefficient of Performance 5.22 3.39 2.83 ∊ (COP) A Heating output B Refrigerating capacity C Power consumption = 35 °C = 45 °C = 55 °C = 65 °C VIESMANN VITOCAL 300/350...
Page 23
13.65 12.15 city Power consumption 3.80 5.75 7.25 Coefficient of Performance 5.18 3.37 2.68 ∊ (COP) A Heating output B Refrigerating capacity C Power consumption = 35 °C = 45 °C = 55 °C = 65 °C VIESMANN VITOCAL 300/350...
Page 24
Never use zinc-plated/galvanised pipes for the brine circuits. Heat transfer medium Order the required amount of Tyfocor for the entire system. Never dilute the premixed heat transfer medium with water (min. frost protection down to –15 °C). VIESMANN VITOCAL 300/350...
Page 25
Vitocell 100-V, type CVA (from 300 l capacity) in conjunction with a Vitotrans 100 plate-type heat exchanger (for further details, see the technical guide). Tested quality CE designation according to current EC Directives. International quality seal for heat pumps. Töss tested. VIESMANN VITOCAL 300/350...