Electrical Wiring; Ratings & Physical / Electrical Data - Johnson Controls TG9S*MP Installation Manual

Residential gas furnace 95.5% afue single stage multi-position
Hide thumbs Also See for TG9S*MP:
Table of Contents

Advertisement

364861-UIM-H-0712
Table 6: Ratings & Physical / Electrical Data
Nominal
Input
Output
Airflow
MBH kW MBH kW CFM m
40
11.7
38
11.1 800
60
17.6
57
16.7 1000
60
17.6
57
16.7 1200
80
23.4
76
22.3 1200
80
23.4
76
22.3 1600
80
23.4
76
22.3 2200
100 29.3
95
27.8 1600
100 29.3
95
27.8 2000
120 35.1 114
33.4 1600
120 35.1 114
33.4 2000
130 38.1 123.5 36.2 2000
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
SUPPLY VOLTAGE CONNECTIONS
Junction
Box
Connect ground
lead to screw
Electrical Entry
BLK
L1-Hot
WHT
Neutral
FIGURE 17: Electrical Wiring
1. Provide a power supply separate from all other circuits. Install over-
current protection and disconnect switch per local/national electrical
codes. The switch should be close to the unit for convenience in
servicing. With the disconnect or fused switch in the OFF position,
check all wiring against the unit wiring label. Refer to the wiring dia-
gram in this instruction.
2. Remove the wiring box cover screws. Route all power wiring
through a conduit connector or other proper bushing that has been
installed into the unit opening and the junction box. In the junction
box there is a black wire, a white wire and a green ground screw.
Connect the power supply as shown on the unit's wiring label on
the inside of the blower compartment door or the wiring schematic
in this section. Connect the black wire to L1 (hot) from the power
supply. Connect the white wired to neutral. Connect the ground wire
(installer-supplied) to the green (equipment ground) screw. An
alternate wiring method is to use a field-provided 2" (5.1 cm) x 4"
(10.2 cm) box and cover on the outside of the furnace. Route the
furnace leads into the box using a protective bushing where the
wires pass through the furnace panel. After making the wiring con-
nections replace the wiring box cover and screws. Refer to Figure
17.
3. The furnace's control system requires correct polarity of the power
supply and a proper ground connection. Refer to Figure 17.
12
Air Temp. Rise
AFUE
%
3
°F
°C
/min
22.7
95.5
30-60
17-33
28.3
95.5
30-60
19-36
34.0
95.5
30-60
19-36
34.0
95.5
35-65
19-36
45.3
95.5
35-65
19-36
62.3
95.5
35-65
19-36
45.3
95.5
35-65
19-36
56.6
95.5
35-65
19-36
45.3
95.5
40-70
22-39
56.6
95.5
35-65
19-36
56.6
95.5
45-75
28-44
Max. Outlet
Blower
Air Temp
°F
°C
HP
Amps
160
71.1
1/3
4.8
160
71.1
1/2
7.07
160
71.1
1/2
7.07
165
73.9
1/2
7.07
165
73.9
3/4
8.8
165
73.9
1
14.5
165
73.9
3/4
8.8
165
73.9
1
14.5
170
76.7
3/4
8.8
165
73.9
1
14.5
175
79.4
1
14.5
The power connection leads and wiring box may be relocated to the
left side of the furnace. Remove the screws and cut wire tie holding
excess wiring. Reposition on the left side of the furnace and fasten
using holes provided.
LOW VOLTAGE CONTROL WIRING CONNECTIONS
Install the field-supplied thermostat by following the instructions that
come with the thermostat. With the thermostat set in the OFF position
and the main electrical source disconnected, connect the thermostat
wiring from the wiring connections on the thermostat to the terminal
board on the ignition module, as shown in Figure 17. Electronic thermo-
stats may require the common wire to be connected. Apply strain relief
to thermostat wires passing through cabinet. If air conditioning equip-
ment is installed, use thermostat wiring to connect the Y and C termi-
nals on the furnace control board to the proper wires on the condensing
unit (unit outside).
Set the heat anticipator in the room thermostat to 0.4 amps. Setting it
lower will cause short cycles. Setting it higher will cause the room
temperature to exceed the set points.
Some electronic thermostats do not have adjustable heat anticipa-
tors. They should be set to six cycles per hour. Follow the thermostat
manufacturer's instructions.
The 24-volt, 40 VA transformer is sized for the furnace components
only, and should not be connected to power auxiliary devices such as
humidifiers, air cleaners, etc. The transformer may provide power for an
air conditioning unit contactor.
Max
Blower
Total Unit
Over-Current
Size
Amps
Protect
11x8
15
8.0
11x8
15
10.0
11x8
15
10.0
11x8
15
10.0
11x10
15
11.5
11x11
20
17.0
11x10
15
11.5
11x11
20
17.0
11x10
15
11.5
11x11
20
17.0
11x11
20
17.0
Johnson Controls Unitary Products
Min. wire Size
(awg) @ 75 ft
one way
14
14
14
14
14
12
14
12
14
12
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gg9s*mp

Table of Contents